2021-11-09 09:07:391ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21101117
 11/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTIONS 212.3 AND 606.1 FBC ACC AND
 PROVIDE DRAWINGS AND DETAILS SHOWING ACCESSIBILITY
 COMPLIANCES FOR THE NEW SINK- CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR EITHER FORWARD OR PARALLEL APPROACH,
 SINK RIM OR COUNTER HEIGHT MEASUREMENT FROM THE
 FINISHED FLOOR, REACH RANGE, AND KNEE AND TOE
 CLEARANCES IF FORWARD APPROACH IS USED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  