| Plan Review Notes For Permit 21101114 |
| Permit Number |
21101114 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-08 13:58:49 | SYSTEM MUST MEET THE REQUIREMENTS OF NFPA 101 CH. 7 | | | | | | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR | | | ASSEMBLIES. | | | DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE | | | PERMITTED TO | | | BE ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, | | | LISTED HARDWARE, | | | PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET: | | | | | | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS | | | AFFIXED TO | | | THE DOOR LEAF. | | | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION | | | THAT IS | | | READILY OPERATED IN THE DIRECTION OF EGRESS. | | | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE | | | HAND | | | IN THE DIRECTION OF EGRESS. | | | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER | | | SUPPLY | | | DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR | | | ASSEMBLY | | | IN THE DIRECTION OF EGRESS. | | | (5)*LOSS OF POWER TO THE LISTED RELEASING HARDWARE | | | AUTOMATICALLY | | | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. | | | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN | | | ACCORDANCE WITH | | | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|