Plan Review Notes
Plan Review Notes For Permit 21101107
Permit Number 21101107
Review Stop B
Sequence Number 3
Notes
Date Text
2022-02-10 13:47:31ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ATTACHMENT DETAIL ON DRAWING A-03 DOES NOT SHOW THE
 ON CENTER SPACING OF THE BASE SHEET ATTACHMENTS FOR THE
 LAP AND NUMBER OF NAILING ROWS AND ON CENTER SPACING IN
 THE FIELD. ROOFING SYSTEM TO BE USED ON THE PROVIDED
 PRODUCT APPROVAL (18-0919.07) REQUIRES ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON
 THE PRODUCT APPROVAL.
  