| Plan Review Notes For Permit 21101107 |
| Permit Number |
21101107 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-02-10 13:47:31 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) ATTACHMENT DETAIL ON DRAWING A-03 DOES NOT SHOW THE | | | ON CENTER SPACING OF THE BASE SHEET ATTACHMENTS FOR THE | | | LAP AND NUMBER OF NAILING ROWS AND ON CENTER SPACING IN | | | THE FIELD. ROOFING SYSTEM TO BE USED ON THE PROVIDED | | | PRODUCT APPROVAL (18-0919.07) REQUIRES ADDITIONAL | | | SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A | | | HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT | | | APPROVAL (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON | | | THE PRODUCT APPROVAL. | | | |
|