Text |
| 2021-11-03 13:59:25 | PLEASE SEE 1ST CYCLE REVIEW NOTES BELOW. | | | | | | 1) THE PERMIT APPLICATION IS FOR AC CHANGE OUT OF 3 | | | LENNOX SYSTEMS W/ DUCTWORK REPLACEMENT BUT THE DRAWING | | | PROVIDED SHOWS ONLY 1 SYSTEM. PLEASE PROVIDE DRAWINGS | | | FOR EACH SYSTEM AS INDICATED ON THE PERMIT APPLICATION. | | | | | | 2) PLEASE PROVIDE DRAWINGS OF THE COMPLETE SYSTEMS | | | INCLUDING THE DUCT SIZES OF EACH DUCT, THE CONDENSATE | | | PIPING, SIZE AND TERMINATION LOCATION ALONG WITH THE | | | CONDENSING UNITS LOCATION AND TIE DOWN METHOD. FBC | | | 107.2.1 | | | | | | 3) THE DESIGNER OF THE DRAWINGS MUST INCLUDE A | | | TITLEBLOCK WHICH HAS THEIR PRINTED NAME AND SIGNATURE. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | |
|