| 2021-11-19 21:44:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. MINIMUM WIRE SIZE FOR 7.5KVA SINGLE PHASE STEP DOWN |
| | TRANSFORMER IS #12 CU. NEC 110.14C1A2 |
| | |
| | 2. PRIMARY OCP FOR 7.5 KVA TRANSFORMER SHOULD BE |
| | 20AMPS. NEC 215.3A, 450.3B1. 240.4 |
| | |
| | 3. SECONDARY OCP FOR 7.5KVA TRANSFORMER SHOULD BE |
| | 40AMPS MAX. NEC 215.3A 408.36 |
| | |
| | 4. EGC SHOWN FROM METER CAN TO SERVICE DISCONNECTING |
| | MEANS. THIS IS A PARALLEL PATH BACK TO GROUNDED |
| | CONDUCTOR. EGC ORIGINATES AT 1ST MEANS OF DISCONNECT ON |
| | LOAD SIDE. PLEASE REMOVE. NEC 250.24 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |