2021-11-03 16:23:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E5.1 45KVA TRANSFORMER:
  
 1) PRIMARY PROTECTION NOT GREATER THAN 125% OF PRIMARY
 CURRENT RATING 215.3(A), T450.3(B)(1), 240.4
  
 2) PRIMARY CONDUCTORS NOT LESS THAN 125% OF THE PRIMARY
 CURRENT RATING 110.14(C)(1)(A)(2), 215.2(A)(1)(A),
 310.15(B)(16)
  
 PAGE E3.1
  
 1) OUTLETS IN COMMON AREAS TO BE TAMPER RESISTANT TYPE
  
 PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE
 WILL SUFFICE. NEC 406.12;