Plan Review Notes
Plan Review Notes For Permit 21101049
Permit Number 21101049
Review Stop M
Sequence Number 1
Notes
Date Text
2021-11-03 17:18:221ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101049
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE AHU REPLACEMENT.
  
 2) SHEET M.1: THE DRAWING SHOWS 1230 SQ FT BUT THE
 FRESH AIR CALCULATIONS SHOW 3211 SQ FT. IS THERE
 ANOTHER AREA THAT IS INCLUDED? IF SO, PLEASE PROVIDE A
 DRAWING WITH THE ENTIRE SQ FT. FBC 107.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE FOR THIS PROJECT. 2020 FBC M 403.3.1.1 AND
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  