| 2021-10-25 11:20:25 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21101008 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS AN APARTMENT BUILDING, PLEASE PROVIDE THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON |
| | MANUAL N. FBC EC C403.2.1 |
| | |
| | 2) AS THIS IS AN APARTMENT BUILDING PLEASE SHOW THE |
| | REQUIRED FIRE SEPARATION BETWEEN TENANTS. HOW IS THE |
| | DUCT WORK FOR THE APARTMENTS ON THE FIRST FLOOR RUN TO |
| | PREVENT THE NEED FOR RADIATION DAMPERS IN THE |
| | CEILING/FLOOR ASSEMBLY? FBC M 607 |
| | |
| | 3) PLEASE SHOW THE DUCTWORK FOR THE BATH EXHAUST FANS |
| | AND THE TERMINATION LOCATIONS. FBC M 501; FBCM 607 |
| | |
| | 4) PLEASE PROVIDE THE DRYER DUCT AND THE TERMINATION |
| | LOCATIONS. HOW IS THIS DRYER DUCT PENETRATING THE FLOOR |
| | OF THE UNIT ABOVE AND HOW ARE YOU PROTECTING THIS |
| | PENETRATION? FBC M 504; FBC M 607 |
| | |
| | 5) IS THERE GOING TO BE A HOOD OVER THE RANGES? IF SO, |
| | ARE THEY DUCTED TO THE OUTDOORS? FBC 107.2.1 |
| | |
| | 6) PLEASE SHOW THE CONDENSATE PIPING FOR EACH |
| | MECHANICAL UNIT AND THE TERMINATION LOCATION. FBC M 307 |
| | |
| | 7) THE TITLE BLOCK FOR THIS PROJECT IS CALLING THIS A |
| | ?PROPOSED RESIDENCE? PLEASE CLARIFY AS THIS IS AN |
| | APARTMENT BUILDING. FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |