| 2022-03-23 10:02:52 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) A FLAME SPREAD TEST REPORT FOR THE LAMINATE FLOOR IT | | | SELF IS NOT REQUIRED. PLEASE PROVIDE THE FLAME SPREAD | | | TEST REPORT FOR THE LAMINATE FLOORING AND THE | | | UNDERLAYMENT AS A SYSTEM - OR - A FLAME SPREAD TEST | | | REPORT FOR THE UNDERLAYMENT IT SELF. | | | | | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | | TO PROJECTDOX ( [email protected] ) | | | |
|