| Plan Review Notes For Permit 21100999 |
| Permit Number |
21100999 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-26 15:42:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE INDICATIONS THAT PART THE MASTER BATHROOM | | | WALL IS A FIRE RATED TENANT SEPARATION WALL. | | | | | | ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED | | | TO THE EXISTING FIRE RATED SEPARATION. | | | | | | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. | | | | | | | | | | | | 2) THERE ARE INDICATIONS OF FLOOR REPLACEMENT IN THE | | | MASTER BEDROMM HOWEVER, THERE ARE NO SPECIFICATIONS | | | SHEETS FOR THE UNDERLAYMENT AND FINISHED FLOOR, THAT | | | INDICATE MEETING THE REQUIREMENTS PER NFPA' | | | | | | THERE IS A CORRECT INDICATION ON SHEET A-102, FOR THE | | | WALL & CEILING FINSISHES; HOWEVER, PRODUCT SPEC SHEETS | | | ARE NEEDED FOR THE OFFICIAL RECORD OF BOTH PRODUCTS. | | | | | | PLEASE REVIEW AND PROVIDE SPEC SHEETS. | | | | | | | | | | | | 3) THE APPLICATION INDICATES APT. 2406 ; HOWEVER, THE | | | PLAN SHEETS INDICATE APT 206. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|