Plan Review Notes
Plan Review Notes For Permit 21100975
Permit Number 21100975
Review Stop E
Sequence Number 1
Notes
Date Text
2021-11-04 09:56:29COMMENTS:
 1) REQUIRE PEDESTAL DETAILS.? 555.19(A)(3), 555.17
 2) 480/277 IS STATED AS THE SYSTEM VOLTAGE. UNCLEAR HOW
 480,240,208 ALL SHOWN AS VOLTAGES FOR PEDESTAL
 RECEPTACLES?
 3) DETAILS ON HOW LOAD CALCULATION IS ARRIVED AT? WHICH
 RECEPTACLES COULD BE IN USE? 555.12
 4) FEEDER CONDUCTOR TAPS ALLOWED FROM FLOATING DOCK
 JUNCTION BOX TO PEDESTALS BY 240.21(B)(5)?4
 5) OVER CURRENT PROTECTION FOR FEEDER TAPS NOT SHOWN.
 240.21(B)(5)(2)
 6) NO DETAIL IS GIVEN FOR THE FLOATING DOCK CABLE
 TRENCH. WILL CONDUCTORS REQUIRE DERATING? PLAN SHOWS AT
 LEAST 48 CURRENT CARING CONDUCTORS.310.15 (B)(3)(A)
 7) PROVIDE SPECIFICATIONS FOR ?G? RATED CABLES IN
 FLOATING DOCK TRENCH. MUST MEET THE CODE REQUIREMENTS
 STATED IN 555.13(2).
 8) WHERE WILL THE SHUNT TRIP CIRCUIT FOR THE GROUND
 FAULT PROTECTION AND EMERGENCY STOP BE POWERED FROM?
 PLEASE PROVIDE SPECIFICATIONS FOR THE FAULT MONITOR AND
 FIELD WIRING DIAGRAM?
 9) PROJECT VALUATION SEEMS A LITTLE LOW. PROVIDE
 CONTRACT
 10)PROVIDE GROUND FAULT PROTECTION ON (2) 1200 AMP MAIN
 DISCONNECTS AS REQUIRED BY 230.95
  
  
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPT.