| Plan Review Notes For Permit 21100968 |
| Permit Number |
21100968 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-27 08:00:06 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL (18-0919.07) REQUIRES ADDITIONAL SIGNED AND | | | SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER | | | FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER | | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL | | | (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON THE | | | PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND | | | DESIGN DATA USED PER 2020 FBC AND ASCE 7-16 - WIND | | | SPEED - EXPOSURE - RISK CATEGORY - ETC. | | | |
|