| 2021-11-02 17:15:12 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. REF. THE WALL LEGEND ON PLAN PAGES A-1 AND A-2 FOR |
| | THE FOLLOWING COMMENT: |
| | THE WALL LEGEND SHOWS THE EXTERIOR LOAD BEARING WALLS |
| | TO BE REMOVED. |
| | PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. WINDOW TYPE ON PAGE A-2 STATES SINGLE HUNG WINDOWS. |
| | NOA 20-0519.09 IS FOR FIXED WINDOWS. |
| | PROVIDE PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 3. NOTE ON PAGE A-2 STATES PROVIDE NEW HURRICANE |
| | SHUTTER. |
| | SUBMIT A SCHEDULE FOR OPENING PROTECTIVE DEVICES OR |
| | ASSEMBLIES. |
| | SUBMIT PRODUCT APPROVALS FOR SHUTTERS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 4. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR |
| | NEW FIREPLACE. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 5. PROVIDE AN EXTERIOR WALL ELEVATION AND DETAIL. SHOW |
| | INTERIOR FINISH, WALL INSULATIUON AND EXTERIOR |
| | CLADDING. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 6. REF. PLAN PAGE A-2 FOR THE FOLLOWING COMMENT: |
| | GROUND FLOOR PLAN HAS A CUT DETAIL 3&4/S-1. THERE IS NO |
| | S-1 PLAN TO REVIEW. |
| | PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | |