2022-08-26 09:14:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NEW SURVEY DOES NOT SHOW THE LOCATION OF THE
 PROPOSED GENERATOR AND THE REQUIRED CLEARANCES.
 THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS.
  