| 2022-02-02 13:48:11 | FAILED |
| | |
| | 1) THANK YOU FOR SHOWING THE MINI-SPLIT UNIT BEING |
| | REMOVED FROM THE REAR OF THE BUILDING. THE NOTES STATE |
| | THAT THIS WILL BE MOVED TO THE ROOF. PLEASE PROVIDE |
| | DRAWINGS, WITH DIMENSIONS, TO VERIFY THAT THE UNIT AND |
| | THE RACK IT IS INSTALLED ON WILL BE SCREENED FROM |
| | PUBLIC VIEW IN ACCORDANCE WITH THE CITYPLACE DRI |
| | REQUIREMENTS. THE LOCATION ON THE ROOF ALSO NEEDS TO BE |
| | SHOWN. |
| | |
| | 2) THE EAST ELEVATION DRAWING SHOWS A 97 SF EXISTING |
| | WINDOW THAT DOES NOT EXIST (BETWEEN THE NEW 97 SF |
| | WINDOW AND THE 142 SF FUTURE STOREFRONT). THIS OPENING |
| | IS NOT SHOWN ON SHEET A1.1.2 THE SOUTH PARTIAL FLOOR |
| | PLAN, NOR IS IT SHOWN ON THE INTERIOR BUILDOUT PERMIT |
| | 21101293 (NOTE AN ALTERNATE OPENING IS SHOWN AT THIS |
| | LOCATION). THE GLAZING SF SHOWN ON SHEET A3.0.1 IS |
| | INCORRECT AND THE REMOVAL OF THE NONEXISTING 97 SF |
| | OPENING WILL REDUCE THE PROVIDED GLAZING TO LESS THAN |
| | THE MINIMUM REQUIRED 60%. CORRECTLY SHOWING THE PERMIT |
| | 2110293 PROPOSED GLAZING MAY RESULT IN MEETING THE 60% |
| | ALLOWANCE. CORRECT INFORMATION MUST BE SHOWN ON ALL THE |
| | PLANS. ADDITIONALLY, THE DIMENSIONS SHOWN ON THE SHELL |
| | PLAN DO NOT MATCH THE DIMENSIONS ON THE BUILD OUT PLAN. |
| | THE BUILD OUT SHOWS LESS WIDTH ON THE EXISTING WINDOW |
| | AND ON THE PROPOSED STOREFRONT. THIS WOULD RESULT IN |
| | NOT ENOUGH GLAZING. |
| | |