2022-02-02 13:48:11FAILED
  
 1) THANK YOU FOR SHOWING THE MINI-SPLIT UNIT BEING
 REMOVED FROM THE REAR OF THE BUILDING. THE NOTES STATE
 THAT THIS WILL BE MOVED TO THE ROOF. PLEASE PROVIDE
 DRAWINGS, WITH DIMENSIONS, TO VERIFY THAT THE UNIT AND
 THE RACK IT IS INSTALLED ON WILL BE SCREENED FROM
 PUBLIC VIEW IN ACCORDANCE WITH THE CITYPLACE DRI
 REQUIREMENTS. THE LOCATION ON THE ROOF ALSO NEEDS TO BE
 SHOWN.
  
 2) THE EAST ELEVATION DRAWING SHOWS A 97 SF EXISTING
 WINDOW THAT DOES NOT EXIST (BETWEEN THE NEW 97 SF
 WINDOW AND THE 142 SF FUTURE STOREFRONT). THIS OPENING
 IS NOT SHOWN ON SHEET A1.1.2 THE SOUTH PARTIAL FLOOR
 PLAN, NOR IS IT SHOWN ON THE INTERIOR BUILDOUT PERMIT
 21101293 (NOTE AN ALTERNATE OPENING IS SHOWN AT THIS
 LOCATION). THE GLAZING SF SHOWN ON SHEET A3.0.1 IS
 INCORRECT AND THE REMOVAL OF THE NONEXISTING 97 SF
 OPENING WILL REDUCE THE PROVIDED GLAZING TO LESS THAN
 THE MINIMUM REQUIRED 60%. CORRECTLY SHOWING THE PERMIT
 2110293 PROPOSED GLAZING MAY RESULT IN MEETING THE 60%
 ALLOWANCE. CORRECT INFORMATION MUST BE SHOWN ON ALL THE
 PLANS. ADDITIONALLY, THE DIMENSIONS SHOWN ON THE SHELL
 PLAN DO NOT MATCH THE DIMENSIONS ON THE BUILD OUT PLAN.
 THE BUILD OUT SHOWS LESS WIDTH ON THE EXISTING WINDOW
 AND ON THE PROPOSED STOREFRONT. THIS WOULD RESULT IN
 NOT ENOUGH GLAZING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]