Plan Review Notes
Plan Review Notes For Permit 21100764
Permit Number 21100764
Review Stop Z
Sequence Number 4
Notes
Date Text
2022-03-24 12:10:421. NOT SATISFIED. REVISED C-13 SHEET SHOW AN ADA RAMP
 GOING DOWN FROM SIDEWALK TO DRIVEWAY LEVEL. THE
 SIDEWALK LEVEL SHALL BE MAINTANED ACROSS DRIVEWAY, THAT
 MEANS THE APRON NEEDS TO REACH THE SIDEWALK LEVEL BY
 THE TIME IS MEETS THE SIDEWALK. PREVIOUS
 COMMENT:SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSSED
 GARAGE DRIVEWAYS ON 8TH AND EUCALYPTUS. PLEASE INCLUDE
 DETAILS IN CIVIL DRAWINGS TO ENSURE COMPLIANCE.
 2. SATISFIED. A PORTION OF THE PUBLIC OPEN SPACE NEEDS
 TO BE INDICATED AS PRIVATE TO COMPLY WITH 25% REQUIRED.
 THE SPACE COULD REMAIN AS PART OF THE PUBLIC OPEN SPACE
 DESIGN, IT JUST NEEDS TO BE SHOWN IN THE CLASSIFICATION
 OF THE PRIVATE TO CONFIRM COMPLIANCE (SHEET A-03)
 3. SATISFIED. ALL CALCULATIONS AND INFORMATION ABOUT
 COMPLIANCE WITH THE OPEN SPACE REQUIREMENTS SHALL BE
 INCLUDED IN THE LANDSCAPE SUBMITTAL.
 4. SATISFIED. PLEASE PROVIDE PHOTOMETRICS TO CONFIRM
 THE 0.6 FOOTCANDLE MINIMUM REQUIRED AT THE CURB ONE
 FOOT ABOVE GRADE IS MET.
 5. SATISFIED. PLEASE ENSURE THE SFX SLIPFITTER IS BEING
 USED.- PREVIOUS COMMENT:PROPOSE STREET LIGHT FIXTURE
 DOES NOT MATCH DOWNTOWN STANDARD. LIGHT FIXTURE TO BE
 INSTALLED ALONG THE STREET SHALL MATCH THE DOWNTOWN
 STANDARD. PLEASE ADJUST.
 6. SATISFIED - PARKING SPACES FOR GUEST AND RETAIL
 SHALL BE INDICATED ON DRAWINGS AND SIGNS SHALL BE
 PROVIDED IN GARAGE. HOW DO GUESTS AND RETAIL CLIENTS
 GET ACCESS THROUGH THE GATE?
 7. SATISFIED.- PLEASE PROVIDE A COMPLETE ELEVATION OF
 THE BRIDGE.
 8. SATISFIED - PLEASE PROVIDE INFORMATION ON THE FDOT
 APPROVAL OF THE PROPOSED CHANGES ALONG DIXIE HIGHWAY.
 9. SATISFIED - COMMENT FOR SOUTH BUILDING - PREVIOUS
 COMMENT:PLEASE PROVIDE INFORMATION ABOUT THE SEATING
 WITHN THE PUBLIC OPEN SPACE AND ANY PRIVATE OPEN SPACE
 LOCATED ALONG THE STREET.
 10. SATISFIED - PLEASE CONFIRM THAT THE SCORE LINE
 PATTERN INCLUDED IN THE SITE PLAN APPROVAL IS
 MAINTAINED.
 11. NOT SATISFIED . FPL TRANSFORMERS ARE ENCROACHING
 MORE THAN 4 FEET INTO THE MINIMUM 15 FEET SIDE SETBACK.
 EQUIPMENT NEEDS TO BE MOVED TOWARDS THE WEST. -
 PREVIOUS COMMENT: PLEASE PROVIDE AN EXHIBIT INDICATING
 THE LOCATION OF ALL ABOVE GROUND UTILITY CONNECTIONS
 LOCATED ALONG THE FRONTAGE LINE. NO ABOVE GROUND
 UTILITIES CAN BE LOCATED WITHIN THE MINIMUM SETBACK.
 12.SATISFIED - A SEPARATE PERMIT SHALL BE SUBMITTED FOR
 LANDSCAPE, IRRIGATION AND STREET LIGHTS.
 13.SATISFIED - PLEASE PROVIDE INFORMATION ABOUT THE
 PROPOSED LIGHTING INSIDE THE GARAGE TO CONFIRM THE
 SOURCE IS HIDDEN FROM EXTERIOR VIEW.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  
  
  
  
  
  
  
  
  
  