| Plan Review Notes For Permit 21100764 |
| Permit Number |
21100764 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-04-27 06:30:02 | APPOVED WITH PRIVISO: | | | | | | SHEET M-4.1.2: KEYNOTES 9 AND 12 ARE FOR FUTURE BUT THE | | | OUTDOOR AIR IS REQUIRED NOW FOR UNIT B-1. THE DEN HAS A | | | DOOR, WHEN THE DOOR IS CLOSED WE CANNOT OBTAIN THE | | | REQUIRED NATURAL VENTILATION. | | | | | | FMC 402.3 ADJOINING SPACES. WHERE ROOMS AND SPACES | | | WITHOUT OPENINGS TO THE OUTDOORS ARE VENTILATED THROUGH | | | AN ADJOINING ROOM, THE OPENING TO THE ADJOINING ROOMS | | | SHALL BE UNOBSTRUCTED AND SHALL HAVE AN AREA NOT LESS | | | THAN 8 PERCENT OF THE FLOOR AREA OF THE INTERIOR ROOM | | | OR SPACE, BUT NOT LESS THAN 25 SQUARE FEET (2.3 M2). | | | THE MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE | | | BASED ON THE TOTAL FLOOR AREA BEING VENTILATED. |
|