Plan Review Notes
Plan Review Notes For Permit 21100764
Permit Number 21100764
Review Stop M
Sequence Number 3
Notes
Date Text
2022-04-27 06:30:02APPOVED WITH PRIVISO:
  
 SHEET M-4.1.2: KEYNOTES 9 AND 12 ARE FOR FUTURE BUT THE
 OUTDOOR AIR IS REQUIRED NOW FOR UNIT B-1. THE DEN HAS A
 DOOR, WHEN THE DOOR IS CLOSED WE CANNOT OBTAIN THE
 REQUIRED NATURAL VENTILATION.
  
 FMC 402.3 ADJOINING SPACES. WHERE ROOMS AND SPACES
 WITHOUT OPENINGS TO THE OUTDOORS ARE VENTILATED THROUGH
 AN ADJOINING ROOM, THE OPENING TO THE ADJOINING ROOMS
 SHALL BE UNOBSTRUCTED AND SHALL HAVE AN AREA NOT LESS
 THAN 8 PERCENT OF THE FLOOR AREA OF THE INTERIOR ROOM
 OR SPACE, BUT NOT LESS THAN 25 SQUARE FEET (2.3 M2).
 THE MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE
 BASED ON THE TOTAL FLOOR AREA BEING VENTILATED.