| 2022-03-11 13:47:48 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21100764 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-4.1.2: PLEASE SHOW HOW THE NATURAL |
| | VENTILATION WILL BE SUPPLIED TO THE DEN IN UNIT B1 |
| | |
| | 2) SHEET M-4.1.2: KEYNOTES 9 AND 12 ARE FOR FUTURE BUT |
| | THE OUTDOOR AIR IS REQUIRED NOW FOR UNIT |
| | B-1 |
| | |
| | 3) SHEET M-6.2.3: PLEASE USE THE OCCUPANCY |
| | CLASSIFICATION FROM TABLE 403.3.1.1 TO IDENTIFY THE |
| | FITNESS AREA AND THE YOGA ROOM I.E. HEALTH CLUB/WEIGHT |
| | ROOM OR HEALTH CLUB/AEROBICS ROOM. I CANNOT VERIFY THE |
| | OUTDOOR AIR CALCULATIONS UNTIL THESE OCCUPANCIES HAVE |
| | BEEN ADDED. PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS |
| | FOR EACH OCCUPANCY CLASSIFICATION BASED ON FBC M |
| | 403.3.1.1 AND THEN TABLE 403.3.1.1. THE TABLE MUST BE |
| | USED AND NOT THE EGRESS OCCUPANT COUNT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |