Plan Review Notes
Plan Review Notes For Permit 21100762
Permit Number 21100762
Review Stop B
Sequence Number 2
Notes
Date Text
2022-03-09 13:52:30NEW RESIDENTIAL 8 STORY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) POOL BARRIER GATE SHOWN ON DRAWING 064 L3-4-05
 SHOULD BE 48" HIGH PER FBC 454.1.3.1.9
  
 2) PLEASE SEE THE EXCEPTIONS - THE FIRE RATING OF THE
 WALLS SHOULD BE THE SAME (STAIR AND CORRIDOR) - - STAIR
 NUMBER 3 SHOULD NOT TERMINATE AT A 1 HR RATED CORRIDOR
 - FBC 1023.3 TERMINATION.
 INTERIOR EXIT STAIRWAYS AND RAMPS SHALL TERMINATE AT AN
 EXIT DISCHARGE OR A PUBLIC WAY.
  
 EXCEPTIONS: 1.NOT MORE THAN 50 PERCENT OF THE NUMBER
 AND MINIMUM WIDTH OR REQUIRED CAPACITY OF INTERIOR EXIT
 STAIRWAYS AND RAMPS IS PERMITTED TO EGRESS THROUGH
 AREAS ON THE LEVEL OF DISCHARGE PROVIDED ALL OF THE
 FOLLOWING CONDITIONS ARE MET:
  
 1.2.THE ENTIRE AREA OF THE LEVEL OF EXIT DISCHARGE IS
 SEPARATED FROM AREAS BELOW BY CONSTRUCTION CONFORMING
 TO THE FIRE-RESISTANCE RATING FOR THE ENCLOSURE.
  
 1.3.THE EGRESS PATH FROM THE INTERIOR EXIT STAIRWAY AND
 RAMP ON THE LEVEL OF EXIT DISCHARGE IS PROTECTED
 THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
 PORTIONS OF THE LEVEL OF EXIT DISCHARGE WITH ACCESS TO
 THE EGRESS PATH SHALL BE EITHER EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, OR
 SEPARATED FROM THE EGRESS PATH IN ACCORDANCE WITH THE
 REQUIREMENTS FOR THE ENCLOSURE OF INTERIOR EXIT
 STAIRWAYS OR RAMPS.
  
 1.4.WHERE A REQUIRED INTERIOR EXIT STAIRWAY OR RAMP AND
 AN EXIT ACCESS STAIRWAY OR RAMP SERVE THE SAME FLOOR
 LEVEL AND TERMINATE AT THE SAME LEVEL OF EXIT
 DISCHARGE, THE TERMINATION OF THE EXIT ACCESS STAIRWAY
 OR RAMP AND THE EXIT DISCHARGE DOOR OF THE INTERIOR
 EXIT STAIRWAY OR RAMP SHALL BE SEPARATED BY A DISTANCE
 OF NOT LESS THAN 30 FEET (9144 MM) OR NOT LESS THAN
 ONE-FOURTH THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING, WHICHEVER IS LESS. THE
 DISTANCE SHALL BE MEASURED IN A STRAIGHT LINE BETWEEN
 THE EXIT DISCHARGE DOOR FROM THE INTERIOR EXIT STAIRWAY
 OR RAMP AND THE LAST TREAD OF THE EXIT ACCESS STAIRWAY
 OR TERMINATION OF SLOPE OF THE EXIT ACCESS RAMP.
  
 3) PLEASE SHOW THAT DOORS THAT OPEN INTO THE EXIT
 ACCESS CORRIDORS SUCH AS GROUND FLOOR DOOR AT STAIR #3
 DOOR (S116) AND ELECTRIC. ROOM DOOR (S126.1) COMPLY
 WITH FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 4) DRAWING A-10.2.2 - UNIT C3 - PLEASE SHOW THAT THE
 WALLS AROUND THE SHOWER AT THE FAUCET REQUIRE GRAB BAR
 BACKING FBC ACCESSIBILITY FAIR HOUSING.
  
 5) ON THE UNIT PLAN THE CORRIDOR WALLS ARE MARKED AS
 WALL #4 - THE WALL SCHEDULE FOR WALL #4 DOES NOT SHOW
 THE REQUIRED STC REQUIREMENT. PLEASE SHOW HOW THE STC
 SOUND RATING IS PROVIDED FOR THE WALLS - WHERE REQUIRED
 PER FBC 1207.2 AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE
 SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY
 ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND
 TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST
 PROCEDURES SET FORTH IN ASTM E90.
  
 6) ON THE UNIT PLANS SOME OF THE WALLS BETWEEN THE
 CORRIDOR AND UNITS ARE SHOWN TO BE FIRE RATED SOME ARE
 NOT - PLEASE CORRECT.
  
 7) THE EGRESS CORRIDOR BESIDE STAIR #3 SHOWS THE FLOOR
 TO BE RAMPED AND ALSO SHOWS STAIR ON THE RAMP - PLEASE
 CLARIFY
  
 8) DRAWING A-5.2.2 DETAIL 13 - SHOWS GRAB BAR HEIGHT AT
 3'3" - TYPO?
  
 9) THE STRUCTURAL DRAWINGS NEED TO SHOW - - THRESHOLD
 BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT 110.8.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
  
  
  
  
  
  
  
  
  
  
  
  