| 2022-03-09 13:52:30 | NEW RESIDENTIAL 8 STORY |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) POOL BARRIER GATE SHOWN ON DRAWING 064 L3-4-05 |
| | SHOULD BE 48" HIGH PER FBC 454.1.3.1.9 |
| | |
| | 2) PLEASE SEE THE EXCEPTIONS - THE FIRE RATING OF THE |
| | WALLS SHOULD BE THE SAME (STAIR AND CORRIDOR) - - STAIR |
| | NUMBER 3 SHOULD NOT TERMINATE AT A 1 HR RATED CORRIDOR |
| | - FBC 1023.3 TERMINATION. |
| | INTERIOR EXIT STAIRWAYS AND RAMPS SHALL TERMINATE AT AN |
| | EXIT DISCHARGE OR A PUBLIC WAY. |
| | |
| | EXCEPTIONS: 1.NOT MORE THAN 50 PERCENT OF THE NUMBER |
| | AND MINIMUM WIDTH OR REQUIRED CAPACITY OF INTERIOR EXIT |
| | STAIRWAYS AND RAMPS IS PERMITTED TO EGRESS THROUGH |
| | AREAS ON THE LEVEL OF DISCHARGE PROVIDED ALL OF THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | |
| | 1.2.THE ENTIRE AREA OF THE LEVEL OF EXIT DISCHARGE IS |
| | SEPARATED FROM AREAS BELOW BY CONSTRUCTION CONFORMING |
| | TO THE FIRE-RESISTANCE RATING FOR THE ENCLOSURE. |
| | |
| | 1.3.THE EGRESS PATH FROM THE INTERIOR EXIT STAIRWAY AND |
| | RAMP ON THE LEVEL OF EXIT DISCHARGE IS PROTECTED |
| | THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM. |
| | PORTIONS OF THE LEVEL OF EXIT DISCHARGE WITH ACCESS TO |
| | THE EGRESS PATH SHALL BE EITHER EQUIPPED THROUGHOUT |
| | WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, OR |
| | SEPARATED FROM THE EGRESS PATH IN ACCORDANCE WITH THE |
| | REQUIREMENTS FOR THE ENCLOSURE OF INTERIOR EXIT |
| | STAIRWAYS OR RAMPS. |
| | |
| | 1.4.WHERE A REQUIRED INTERIOR EXIT STAIRWAY OR RAMP AND |
| | AN EXIT ACCESS STAIRWAY OR RAMP SERVE THE SAME FLOOR |
| | LEVEL AND TERMINATE AT THE SAME LEVEL OF EXIT |
| | DISCHARGE, THE TERMINATION OF THE EXIT ACCESS STAIRWAY |
| | OR RAMP AND THE EXIT DISCHARGE DOOR OF THE INTERIOR |
| | EXIT STAIRWAY OR RAMP SHALL BE SEPARATED BY A DISTANCE |
| | OF NOT LESS THAN 30 FEET (9144 MM) OR NOT LESS THAN |
| | ONE-FOURTH THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL |
| | DIMENSION OF THE BUILDING, WHICHEVER IS LESS. THE |
| | DISTANCE SHALL BE MEASURED IN A STRAIGHT LINE BETWEEN |
| | THE EXIT DISCHARGE DOOR FROM THE INTERIOR EXIT STAIRWAY |
| | OR RAMP AND THE LAST TREAD OF THE EXIT ACCESS STAIRWAY |
| | OR TERMINATION OF SLOPE OF THE EXIT ACCESS RAMP. |
| | |
| | 3) PLEASE SHOW THAT DOORS THAT OPEN INTO THE EXIT |
| | ACCESS CORRIDORS SUCH AS GROUND FLOOR DOOR AT STAIR #3 |
| | DOOR (S116) AND ELECTRIC. ROOM DOOR (S126.1) COMPLY |
| | WITH FBC 1005.7.1 DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | |
| | 4) DRAWING A-10.2.2 - UNIT C3 - PLEASE SHOW THAT THE |
| | WALLS AROUND THE SHOWER AT THE FAUCET REQUIRE GRAB BAR |
| | BACKING FBC ACCESSIBILITY FAIR HOUSING. |
| | |
| | 5) ON THE UNIT PLAN THE CORRIDOR WALLS ARE MARKED AS |
| | WALL #4 - THE WALL SCHEDULE FOR WALL #4 DOES NOT SHOW |
| | THE REQUIRED STC REQUIREMENT. PLEASE SHOW HOW THE STC |
| | SOUND RATING IS PROVIDED FOR THE WALLS - WHERE REQUIRED |
| | PER FBC 1207.2 AIRBORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE |
| | SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY |
| | ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND |
| | TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST |
| | PROCEDURES SET FORTH IN ASTM E90. |
| | |
| | 6) ON THE UNIT PLANS SOME OF THE WALLS BETWEEN THE |
| | CORRIDOR AND UNITS ARE SHOWN TO BE FIRE RATED SOME ARE |
| | NOT - PLEASE CORRECT. |
| | |
| | 7) THE EGRESS CORRIDOR BESIDE STAIR #3 SHOWS THE FLOOR |
| | TO BE RAMPED AND ALSO SHOWS STAIR ON THE RAMP - PLEASE |
| | CLARIFY |
| | |
| | 8) DRAWING A-5.2.2 DETAIL 13 - SHOWS GRAB BAR HEIGHT AT |
| | 3'3" - TYPO? |
| | |
| | 9) THE STRUCTURAL DRAWINGS NEED TO SHOW - - THRESHOLD |
| | BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT 110.8.4.4 |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |