| 2021-11-30 10:57:26 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21100762 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-2.2.1: PLEASE ADD A NOTE ON THE DRAWING |
| | STATING THAT THE GENERATOR WILL REQUIRE A SEPARATE |
| | PERMIT APPLICATION AND PLAN REVIEW AS IT WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. |
| | |
| | 2) SHEET M-2.2.5: PLEASE SHOW THE MECHANICAL UNITS WILL |
| | BE A MINIMUM OF 10 FEET FROM THE ROOFS EDGE OR MEET THE |
| | GUARDS REQUIREMENT IN FBC M 304.11 |
| | |
| | 3) THE DUCT WORK SERVING THE ELECTRICAL ROOMS ON EACH |
| | FLOOR IS PENETRATING A FIRE RATED WALL, PLEASE SHOW THE |
| | FIRE DAMPER FOR THESE PENETRATIONS ON EACH FLOOR. FBC M |
| | 607 |
| | |
| | 4) PLEASE PROVIDE THE NATURAL VENTILATION CALCULATIONS |
| | FOR EACH UNIT. FBC M 402.2 AND 402.3 |
| | |
| | 5) PLEASE SHOW THE EXHAUST TERMINATION LOCATIONS ARE 3 |
| | FEET FROM OPERABLE OPENINGS. FBC M 501.3 |
| | |
| | 6) SHEET M-4.2.1: UNIT MICRO, UNIT A2, UNIT A3, UNIT |
| | A4- PLEASE SHOW WHERE THE NATURAL VENTILATION SOURCE |
| | WILL BE IN THESE UNITS AS I DO NOT SEE ANY OPERABLE |
| | WINDOWS. FBC 402.2 AND 402.3 |
| | |
| | 7) SHEET M-4.2.2: UNIT C3, UNIT C3.2- PLEASE SHOW WHERE |
| | THE NATURAL VENTILATION SOURCE WILL BE IN THESE UNITS |
| | AS I DO NOT SEE ANY OPERABLE WINDOWS. FBC 402.2 AND |
| | 402.3 |
| | |
| | 8) SHEET M-4.2.3: UNIT C4, UNIT C5- PLEASE SHOW WHERE |
| | THE NATURAL VENTILATION SOURCE WILL BE IN THESE UNITS |
| | AS I DO NOT SEE ANY OPERABLE WINDOWS. FBC 402.2 AND |
| | 402.3 |
| | |
| | 9) SHEET M-4.1.2: UNIT B1 DRYER DUCT INDICATES A TOTAL |
| | OF 4 90 DEGREE ELBOWS AND 2 45 DEGREE ELBOWS. THE DRYER |
| | DUCT CHART SHOWN ON THE DRAWING DOES NOT PROVIDE A |
| | LENGTH FOR THIS DESIGN. PLEASE PROVIDE INFORMATION FROM |
| | THE DRYER MANUFACTURER SHOWING A DESIGN FOR THIS MANY |
| | 90?S AND 45?S. |
| | |
| | 10) SHEET M-4.1.2: PLEASE SHOW WHERE THE NATURAL |
| | VENTILATION SOURCE WILL BE IN UNITS B1 MASTER BEDROOM, |
| | UNIT C3 BOTH BEDROOMS. . FBC M 402.2 AND 402.3 |
| | |
| | 11) SHEET M-6.2.3: PLEASE PROVIDE OUTDOOR AIR |
| | CALCULATIONS BY IDENTIFYING EACH USE OF SPACE INCLUDING |
| | CORRIDORS BASED ON THE OCCUPANCY CLASSIFICATIONS OF FBC |
| | M TABLE 403.3.1.1 AND 403.3.1.1. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |