2021-11-23 14:54:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.2 - THERE IS ARE INDICATIONS OF 2 EXITS
 FROM THE POOL DECK WITH 46" WIDTH AST EACH EXIT.
  
 THE TOTAL OCCUPANCY PROPOSED IS 41 FOR THE POOL + 390
 FOR THE POOL DECK68 FOR THE LOUNGE = 499.
  
 THE TOTAL OCUPANCY LOAD FOR THE EXITS IS 46"X 2 /.2=
 460.
  
 THERE IS INSUFFICIENT EXIT WIDTH FOR THE POOL DECK.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAIL
 NARRATIVE, CODE REFERNECES AND DETAILED OCCUPANCY LOAD
 CALCULATIONS.
  
  
  
 2) SHEET C 17 - ALL FIRE LINE UNDERGROUND INCLUDING
 FDC, DDCV AND PRIVATE FIRE HYDRANTS SHALL BE INSTALLED
 PER NFPA 24 BY A FLORIDA CERTIFIED UNDERGROUND
 CONTRACTOR AND UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGMENT.
  
  
  
 3) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE
 FOR EMERGENCY RADIO COMMUNICATIONS.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT
 SYSTEMS.
 24.9.1 GENERAL.
 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM
 CAPABLE
 OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON
 FREQUENCIES
 ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE
 INSTALLED
 WITHOUT PRIOR COORDINATION AND APPROVAL OF THE
 AUTHORITY
 HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL
 SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT
 DEGRADE
 THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM.
 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED
 FOR
 APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF
 SUCCESSFUL
 ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED
 FOR THE
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED
 BY
 THE AUTHORITY HAVING JURISDICTION.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT.
  
  
  
 4) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE
 FOR A FIRE ALARM SYSTEM.
  
 PER F.A.C. 61 G
  
 PLEASE PROVIDE FOR A FIRE LARM SYSTEM TO BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 5) SHEET FIRE SPRINKLER - THERE IS NO INDICATION TO
 PROVIDE FOR A FIRE SPRINKLER SYSTEM.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 THIS INFORMATION SHALL BE PROVIDED IN THIS MASTER PERMI
 WITH SHOP DRAWINGS BEING SUBMITTED UNDER SEPARATE
 PERMIT.
  
 PLEASE PROVIDE THE REQUIRED FS DOCUMENTS IN PLAN
 DRAWINGS OR NARRATIVE FORM SIGNED AND SELAED BY THE
 EOR.
  
  
  
 6) SHEET A 2 2 1 - THERE IS AN INDICATION OF AN
 ELECTRIC FIRE PUMP AND A GENERATOR.
  
 PLEASE PROVIDE CLARIFICATION/VERIFICATION THAT THE FIRE
 PUMP IS BACKED-UP BY THE GENERATOR AS REQUIRED BY NFPA
 20 & 70.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  