| 2021-11-23 14:54:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 1.2 - THERE IS ARE INDICATIONS OF 2 EXITS |
| | FROM THE POOL DECK WITH 46" WIDTH AST EACH EXIT. |
| | |
| | THE TOTAL OCCUPANCY PROPOSED IS 41 FOR THE POOL + 390 |
| | FOR THE POOL DECK68 FOR THE LOUNGE = 499. |
| | |
| | THE TOTAL OCUPANCY LOAD FOR THE EXITS IS 46"X 2 /.2= |
| | 460. |
| | |
| | THERE IS INSUFFICIENT EXIT WIDTH FOR THE POOL DECK. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE A DETAIL |
| | NARRATIVE, CODE REFERNECES AND DETAILED OCCUPANCY LOAD |
| | CALCULATIONS. |
| | |
| | |
| | |
| | 2) SHEET C 17 - ALL FIRE LINE UNDERGROUND INCLUDING |
| | FDC, DDCV AND PRIVATE FIRE HYDRANTS SHALL BE INSTALLED |
| | PER NFPA 24 BY A FLORIDA CERTIFIED UNDERGROUND |
| | CONTRACTOR AND UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 3) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE |
| | FOR EMERGENCY RADIO COMMUNICATIONS. |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| | SYSTEMS. |
| | 24.9.1 GENERAL. |
| | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| | CAPABLE |
| | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| | FREQUENCIES |
| | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| | INSTALLED |
| | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| | AUTHORITY |
| | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| | DEGRADE |
| | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED |
| | FOR |
| | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| | SUCCESSFUL |
| | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| | FOR THE |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| | BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST |
| | PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN |
| | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES |
| | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE |
| | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, [email protected], |
| | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR |
| | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 4) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE |
| | FOR A FIRE ALARM SYSTEM. |
| | |
| | PER F.A.C. 61 G |
| | |
| | PLEASE PROVIDE FOR A FIRE LARM SYSTEM TO BE INSTALLED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | |
| | 5) SHEET FIRE SPRINKLER - THERE IS NO INDICATION TO |
| | PROVIDE FOR A FIRE SPRINKLER SYSTEM. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | THIS INFORMATION SHALL BE PROVIDED IN THIS MASTER PERMI |
| | WITH SHOP DRAWINGS BEING SUBMITTED UNDER SEPARATE |
| | PERMIT. |
| | |
| | PLEASE PROVIDE THE REQUIRED FS DOCUMENTS IN PLAN |
| | DRAWINGS OR NARRATIVE FORM SIGNED AND SELAED BY THE |
| | EOR. |
| | |
| | |
| | |
| | 6) SHEET A 2 2 1 - THERE IS AN INDICATION OF AN |
| | ELECTRIC FIRE PUMP AND A GENERATOR. |
| | |
| | PLEASE PROVIDE CLARIFICATION/VERIFICATION THAT THE FIRE |
| | PUMP IS BACKED-UP BY THE GENERATOR AS REQUIRED BY NFPA |
| | 20 & 70. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |