2022-01-06 11:01:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.5.2.1
  
 1) FEED TO FIRE PUMP CONTROLLER SHOWS NO WIRE SIZES
 FROM FPL TRANSFORMER.
  
 2) FAULT CURRENT CALCULATION NOT SHOWN FOR SERVICE AND
 FEEDERS. 110.9, 110.10
  
 3) EMERGENCY RISER NOT SHOWN. PLEASE INDICATE THE WIRE
 SIZES ON THE RISER.
  
 4) PANEL UDP HAS 1200, AND 2000 AMPERE MAINS PLEASE
 SHOW HOW 240.87 COMPLIANCE WILL BE HANDLED.
 PANEL DPS HAS A 1400 AMPERS MAIN PLEASE SHOW HOW 240.87
 COMPLIANCE WILL BE HANDLED.
  
 5) RISER SHOWS ELEVATOR 1 AND 2 BUT PLANS ONLY SHOW
 ELEVATORS 3 AND 4.
  
 6) ELEVATORS ARE SHOWN BEING CONNECTED TO PANEL ERN
 WHICH IS NOT SHOWN ON THIS RISER.
  
 6) RISER DOES NOT SPECIFY WHAT SIZE GENERATOR IS BEING
 USED, GENERATOR PAGE E.7.2.3 SHOWS TWO GENERATORS?
  
 7) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING
 SYSTEMS. LOW VOLTAGE, FIRE ALARM, GENERATOR, POOL, BDA
  
 PAGE E4.2.1
  
 1) UNITS A1, A1.1, A2, A3 NEED ADDITIONAL OUTLETS IN
 KITCHEN BETWEEN STOVE AND SINK. 210.52
  