| Plan Review Notes For Permit 21100762 |
| Permit Number |
21100762 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-06 11:01:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E.5.2.1 | | | | | | 1) FEED TO FIRE PUMP CONTROLLER SHOWS NO WIRE SIZES | | | FROM FPL TRANSFORMER. | | | | | | 2) FAULT CURRENT CALCULATION NOT SHOWN FOR SERVICE AND | | | FEEDERS. 110.9, 110.10 | | | | | | 3) EMERGENCY RISER NOT SHOWN. PLEASE INDICATE THE WIRE | | | SIZES ON THE RISER. | | | | | | 4) PANEL UDP HAS 1200, AND 2000 AMPERE MAINS PLEASE | | | SHOW HOW 240.87 COMPLIANCE WILL BE HANDLED. | | | PANEL DPS HAS A 1400 AMPERS MAIN PLEASE SHOW HOW 240.87 | | | COMPLIANCE WILL BE HANDLED. | | | | | | 5) RISER SHOWS ELEVATOR 1 AND 2 BUT PLANS ONLY SHOW | | | ELEVATORS 3 AND 4. | | | | | | 6) ELEVATORS ARE SHOWN BEING CONNECTED TO PANEL ERN | | | WHICH IS NOT SHOWN ON THIS RISER. | | | | | | 6) RISER DOES NOT SPECIFY WHAT SIZE GENERATOR IS BEING | | | USED, GENERATOR PAGE E.7.2.3 SHOWS TWO GENERATORS? | | | | | | 7) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING | | | SYSTEMS. LOW VOLTAGE, FIRE ALARM, GENERATOR, POOL, BDA | | | | | | PAGE E4.2.1 | | | | | | 1) UNITS A1, A1.1, A2, A3 NEED ADDITIONAL OUTLETS IN | | | KITCHEN BETWEEN STOVE AND SINK. 210.52 | | | |
|