| 2021-12-21 14:22:39 | NEW RESIDENTIAL 8 STORY |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT). |
| | |
| | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR |
| | DOORS, ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS |
| | NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD FBC WPB 107.3.4 |
| | |
| | 3) POOL BARRIER GATE SHOWN ON DRAWING 064 L3-4-05 |
| | SHOULD BE 48" HIGH PER FBC 454.1.3.1.9 |
| | |
| | 4) STAIR NUMBER 3 SHOULD NOT TERMINATE AT A 1 HR RATED |
| | CORRIDOR - FBC 1023.3 TERMINATION. |
| | INTERIOR EXIT STAIRWAYS AND RAMPS SHALL TERMINATE AT AN |
| | EXIT DISCHARGE OR A PUBLIC WAY. |
| | |
| | 5) PLEASE SHOW THAT DOORS THAT OPEN INTO THE EXIT |
| | ACCESS CORRIDORS SUCH AS DOOR S226, SX25 ETC. COMPLY |
| | WITH FBC 1005.7.1 DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | |
| | 6) DRAWING A-10.2.1 - UNIT A4 - PLEASE SHOW THAT THE |
| | WALLS AROUND THE TOILET REQUIRE GRAB BAR BACKING FBC |
| | ACCESSIBILITY FAIR HOUSING. |
| | |
| | 7) PLEASE SHOW HOW THE STC SOUND RATING IS PROVIDED FOR |
| | THE WALLS - WHERE REQUIRED PER FBC 1207.2 AIRBORNE |
| | SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE |
| | SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY |
| | ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND |
| | TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST |
| | PROCEDURES SET FORTH IN ASTM E90. |
| | |
| | 8) FOR THE FINISH FLOORING IN THE UNITS ABOVE THE 1ST |
| | FLOOR - OTHER THAN CARPET - 1) THE FOLLOWING ACUSTICAL |
| | TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | 9) DEFERRED SUBMITTALS NEED TO BE LISTED ON THE |
| | DRAWINGS - FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10) PLEASE SHOW COMMON AREA RESTROOM WALLS AND BASE |
| | BOARDS TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, |
| | FBC 1210.2.1FLOORS AND WALL BASES. |
| | IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| | SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| | FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| | WALLS NOT LESS THAN 4 INCHES (102 MM). (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 11) PLEASE SHOW THE WIDTH OF STAIR NUMBER 3 - FBC |
| | 1011.2 WIDTH AND CAPACITY. |
| | THE REQUIRED CAPACITY OF STAIRWAYS SHALL BE DETERMINED |
| | AS SPECIFIED IN SECTION 1005.1, BUT THE MINIMUM WIDTH |
| | SHALL BE NOT LESS THAN 44 INCHES (1118 MM). |
| | |