Plan Review Notes
Plan Review Notes For Permit 21100762
Permit Number 21100762
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-21 14:22:39NEW RESIDENTIAL 8 STORY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT).
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS
 NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD FBC WPB 107.3.4
  
 3) POOL BARRIER GATE SHOWN ON DRAWING 064 L3-4-05
 SHOULD BE 48" HIGH PER FBC 454.1.3.1.9
  
 4) STAIR NUMBER 3 SHOULD NOT TERMINATE AT A 1 HR RATED
 CORRIDOR - FBC 1023.3 TERMINATION.
 INTERIOR EXIT STAIRWAYS AND RAMPS SHALL TERMINATE AT AN
 EXIT DISCHARGE OR A PUBLIC WAY.
  
 5) PLEASE SHOW THAT DOORS THAT OPEN INTO THE EXIT
 ACCESS CORRIDORS SUCH AS DOOR S226, SX25 ETC. COMPLY
 WITH FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 6) DRAWING A-10.2.1 - UNIT A4 - PLEASE SHOW THAT THE
 WALLS AROUND THE TOILET REQUIRE GRAB BAR BACKING FBC
 ACCESSIBILITY FAIR HOUSING.
  
 7) PLEASE SHOW HOW THE STC SOUND RATING IS PROVIDED FOR
 THE WALLS - WHERE REQUIRED PER FBC 1207.2 AIRBORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE
 SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY
 ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND
 TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST
 PROCEDURES SET FORTH IN ASTM E90.
  
 8) FOR THE FINISH FLOORING IN THE UNITS ABOVE THE 1ST
 FLOOR - OTHER THAN CARPET - 1) THE FOLLOWING ACUSTICAL
 TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 9) DEFERRED SUBMITTALS NEED TO BE LISTED ON THE
 DRAWINGS - FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10) PLEASE SHOW COMMON AREA RESTROOM WALLS AND BASE
 BOARDS TO COMPLY WITH FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR,
 FBC 1210.2.1FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM). (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 11) PLEASE SHOW THE WIDTH OF STAIR NUMBER 3 - FBC
 1011.2 WIDTH AND CAPACITY.
 THE REQUIRED CAPACITY OF STAIRWAYS SHALL BE DETERMINED
 AS SPECIFIED IN SECTION 1005.1, BUT THE MINIMUM WIDTH
 SHALL BE NOT LESS THAN 44 INCHES (1118 MM).
  