| Plan Review Notes For Permit 21100754 |
| Permit Number |
21100754 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-22 15:36:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE | | | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL | | | PROPOSED VINYL FLOORING. | | | | | | VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT | | | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. | | | | | | PER NFPA 101 | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT | | | SPEC SHEETS OF THE PROPOSED FINISHED | | | VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING. | | | | | | | | | 2) THERE ARE INDICATIONS THAT THE BATHROOM WALLS ARE | | | FIRE RATED TENANT/CORRIDOR SEPARATION WALLS. | | | | | | ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED | | | TO THE EXISTING FIRE RATED SEPARATION. | | | | | | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. | | | | | | | | | | | | 3) FOR THE KITCHEN WORK, PROTECT FIRE SPRINKLERS AND | | | FIRE ALARM DEVICES AND EQUIPMENT. | | | | | | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM | | | DEVICES/EQUIPMENT. | | | | | | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|