2021-10-22 15:36:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED FINISHED
 VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THERE ARE INDICATIONS THAT THE BATHROOM WALLS ARE
 FIRE RATED TENANT/CORRIDOR SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED
 TO THE EXISTING FIRE RATED SEPARATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 3) FOR THE KITCHEN WORK, PROTECT FIRE SPRINKLERS AND
 FIRE ALARM DEVICES AND EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709