2022-01-26 14:08:05ELECTRIC PLAN REVIEW FAILED
 1) INCORRECTLY SIZED POOL PANEL FEEDER CONDUCTOR NEC
 310.15 (B)(16)
 2) GROUNDING ELECTRODE SYSTEM TO COMPLY WITH NEC 250
 .50 AND NEC 250.32 (A) EXCEPTION, A NOTE WILL SUFFICE
  
 END OF COMMENTS.
  