| 2021-12-07 09:01:37 | FAILED ELECTRIC REVIEW, SEE COMMENTS BELOW AND CORRECT | | | AS NESSECARY | | | 1) THERE IS NO RISER DIAGRAM SUBMITTED WITH THIS PERMIT | | | AS STATED ON E-01 NEC 215.5 | | | 2) THERE IS NO PANEL SCHEDULES OR LOAD CALCULATIONS | | | SUBMITTED WITH THIS PERMIT AS PER NEC 215.5 | | | 3) RECEPTACLE SPACING IN SOME AREAS MAY BE INADEQUATE | | | AS PER NEC 210.52 | | | 4) THERE ARE NO NOTES IDENTIFYING 120-VOLT BRANCH | | | CIRCUITS TO BE ARC-FAULT PROTECTED AS PER NEC 210.12 | | | 5) THERE IS NO SWITCH SHOWN TO CONTROL FIREPLACE | | | SCONCES FBC 107.23 |
|