| 2021-11-04 11:02:43 | 10/22/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE PERMIT ISSUED REQUIRES A GAS PERMIT FOR THE |
| | TANK-LESS, AND THERE IS NO PERMIT ON FILE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. THE VALUE FOR THE TANKLESS NEEDS TO BE ADDED TO THE |
| | PERMIT PER THE WPB AMENDMENTS TO THE FBC 109.3 BUILDING |
| | PERMITS VALUATIONS. |
| | |
| | 3. WOULD YOU PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 4. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 5. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 6. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| | EHD NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 7. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. IF APPLICABLE, LIST THE BTU LOAD OF EACH APPLIANCE |
| | AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 |
| | FBC FG SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| | THROUGH 402.4 (37) OR 2020 FBC RES. SEC. G2413. |
| | |
| | 9. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2020 FBC RES. SEC. G2413.4.1. |
| | |
| | 10. WOULD YOU PLEASE INDICATE THE SYSTEM'S DELIVERY |
| | PRESSURE (PSI) ON THE PLAN PER THE 2020 FBC FG SEC. |
| | 402.2 OR 2020 FBC RES. SEC. G2413.2. |
| | |
| | 11. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| | OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC |
| | RES. SEC G2421.2. |
| | |
| | 12. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE |
| | ON GAS ISOMERIC PER THE 2020 FBC SEC. G2420.5. |
| | |
| | 13. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | 14. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON |
| | EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE, |
| | DRYERS & OD GRILLS PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 15. THIS TANK-LESS UNIT CALL FOR A 10.5 INCHES WATER |
| | COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCHES |
| | WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | THE MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 16. IF UNITS REQUIRE CONDENSATE, THEY WILL NEED TO BE |
| | 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC R318.5. |
| | |
| | 17. WOULD YOU PLEASE INDICATE ON THE PLAN IF THE |
| | TANK-LESS WATER HEATER IS THE ONLY GAS APPLIANCE IN |
| | THIS SYSTEM? IF NOT, SUBMIT A COMPLETE GAS RISER |
| | SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED |
| | LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE OF GAS, AND |
| | THE TOTAL BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS |
| | ALSO APPLY TO A NEW GAS SYSTEM PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 18. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN SHOW THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 19. A SUB ELECTRICAL PERMIT IS REQUIRED FOR IGNITION |
| | SOURCE PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 20. WOULD YOU PLEASE INDICATE ON THE PLAN IF THE |
| | TANK-LESS WATER HEATER IS REPLACING AN EXISTING |
| | TANK-LESS WATER HEATER, IS IT REPLACING A STORAGE |
| | TANK-TYPE WATER HEATER, OR IS IT BEING ADDED TO THE |
| | EXISTING HOT WATER SYSTEM? INDICATE THE APPLICATION IN |
| | THE DESCRIPTION OF WORK PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |