| 2021-11-30 10:29:58 | ELECTRICAL PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THE LIGHT ABOVE THE SHOWER AREA MUST BE VAPOR PROOF. | | | E4003.9 WET OR DAMP LOCATIONS. | | | LUMINAIRES INSTALLED IN WET OR DAMP LOCATIONS SHALL BE | | | INSTALLED SO THAT WATER CANNOT ENTER OR ACCUMULATE IN | | | WIRING COMPARTMENTS, LAMP HOLDERS OR OTHER ELECTRICAL | | | PARTS. ALL LUMINAIRES INSTALLED IN WET LOCATIONS SHALL | | | BE MARKED SUITABLE FOR WET LOCATIONS. ALL LUMINAIRES | | | INSTALLED IN DAMP LOCATIONS SHALL BE MARKED SUITABLE | | | FOR WET LOCATIONS OR SUITABLE FOR DAMP LOCATIONS. | | | (410.10) | | | | | | INCLUDE VP NEXT TO THE SYMBOL AT THE VAPOR PROOF | | | FIXTURE IN THE SHOWER AREA. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|