| Plan Review Notes For Permit 21100718 |
| Permit Number |
21100718 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-27 11:49:37 | GAS CONTRACTOR CALLED AND RESOLVED MISSING INFORMATION | | | ON THE PLANS. REDLINNED PE PIPE INSTALLED TO POOL | | | HEATER ON PLANS | | 2021-10-26 17:05:23 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21100718 | | | 10/26/2021 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH | | | EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION | | | 2020 | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH | | | EDITION 2020 | | | | | | | | | 1) CLEARLY SHOW THE GAS SUPPLY PIPE SIZE ON THE OUTLET | | | SIDE OF THE GAS METER. THE EXISTING GAS BTU LOAD SHALL | | | BE TAKEN INTO CONSIDERATION WHEN MAKING CALACULATING | | | THIS PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | | | | | | | |
|