2021-10-29 10:25:59ELEVATION CERTIFICATE
 REVIEW COMMENTS
 145 BLOOMFIELD DRIVE
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CORRECTED.
  
 2) CORRECTED.
  
 3) CORRECTED.
  
 4) [THIS INFORMATION WAS ENTERED IN THE WRONG LOCATION.
 THE FLOOD OPENINGS ARE LOCATED IN THE ATTACHED GARAGE,
 WHICH IS ITEM A9.] THERE ARE (4) FLOOD OPENINGS
 SPECIFIED ON THE PLANS AND SHOWN IN THE PHOTOGRAPHS.
 ITEM A9 B) LISTS 0.
  
 5) [THIS INFORMATION WAS ENTERED IN THE WRONG LOCATION.
 THE FLOOD OPENINGS ARE LOCATED IN THE ATTACHED GARAGE,
 WHICH IS ITEM A9. THE PRODUCT EVALUATIONS THAT WERE
 SUBMITTED ARE FOR SMART VENTS. THE INFORMATION FOR THE
 SMART VENTS NEEDS TO BE PROVIDED RATHER THAN THE
 CALCULATIONS FOR THE GREENHECK LOUVERS SHOWN ON THE
 ORIGINAL BUILDING PLANS. THE FLOOD OPENINGS ARE
 REQUIRED TO BE LOCATED NO HIGHER THAN 1.0 FOOT ABOVE
 THE HIGHER OF THE EXTERIOR OR INTERIOR GRADE OR FLOOR
 IMMEDIATELY BELOW THE OPENING. IF THE INTERIOR GRADE
 ELEVATION IS USED, NOTE THIS IN THE COMMENTS AREA OF
 SECTION D. IT SHOULD ALSO BE NOTED IN THE COMMENTS AREA
 OF SECTION D THAT ENGINEERED SMART VENTS ARE INSTALLED.
 ] A9 C) LISTS THE NET AREA OF FLOOD OPENINGS AS 0.0
 SQIN. SHEET A-1.0 OF THE PLANS HAS CALCULATIONS
 SPECIFYING THAT 7448 SQIN OF NET OPENING AREA WILL BE
 PROVIDED.
  
 6) CORRECTED.
  
 7) CORRECTED.
  
 8) CORRECTED.
  
 9) CORRECTED.
  
 10) CORRECTED.
  
 11) [ VERIFY THE CORRECT ELEVATION AND SPECIFY IT ON
 BOTH DOCUMENTS. ] ITEM C2 D) LISTS THE ELEVATION FOR
 THE TOP OF GARAGE SLAB AS 6.6 FT. THE TIE IN SURVEY
 SPECIFIES THE GARAGE ELEVATION AS 6.21' FT. THESE
 ELEVATIONS NEED TO BE CONSISTENT.
  
 12) [ THE EQUIPMENT WILL HAVE TO BE RAISED SO THAT IT
 IS ABOVE THE DFE WHICH IS 8.0' NAVD. ] ITEM C2 E) LISTS
 THE LOWEST ELEVATION OF THE EQUIPMENT SERVICING THE
 BUILDING AS 7.5 FT. THE EQUIPMENT IS REQUIRED TO BE AT
 OR ABOVE THE DFE WHICH IS 8' NAVD.
  
 13) [ ENTER THIS INFORMATION IN THE COMMENTS AREA OF
 SECTION D. ] THE METHOD USED TO DETERMINE LATITUDE AND
 LONGITUDE IS TO BE INDICATED IN THE COMMENTS AREA OF
 SECTION D.
  
 14) [ THE PRODUCT APPROVAL/EVALUATION IS FOR SMART VENT
 ENGINEERED FLOOD VENTS. THESE ARE NOT THE ONES THAT ARE
 SPECIFIED ON THE PLANS. THE PLANS WILL NEED TO BE
 REVISED TO SHOW THE SMART VENTS AND THEIR LOCATIONS. ]
 SUBMIT THE SPECIFICATIONS, EVALUATION REPORT, PRODUCT
 APPROVAL, ETC. FOR THE FLOOD OPENINGS THAT WERE USED.
 THE PHOTOS APPEAR TO SHOW DIFFERENT FLOOD VENTS THAN
 THE GREENHECK LOUVERS THAT ARE SPECIFIED ON THE PLANS.
  
 15) [ PHOTOS OF ELEVATIONS SHOWING THE FLOOD OPENINGS
 ARE REQUIRED. ] NEW PHOTOS OF THE BUILDING SHOWING THE
 FINISH GRADES ARE REQUIRED.
  
 16) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 17) NEW COMMENT. THE BUILDING OWNER'S NAME IN ITEM A1
 IS 145 BLOOMFIELD TRUST. THE CITY'S AND PROPERTY
 APPRAISER'S RECORD HAVE THE OWNER AS PAMELA LOMBA.
 PLEASE CORRECT.
  
 18) NEW COMMENT. ITEM C2 HAS GPS FOR BENCHMARK
 UTILIZED. FEMA'S EC INSTRUCTIONS STATE THAT FOR A GPS
 SURVEY, INDICATE THE BENCHMARK USED FOR THE BASE
 STATION, THE CONTINUOUSLY OPERATING REFERENCE STATIONS
 (CORS) SITES USED FOR AN ON-LINE POSITIONING USER
 SERVICE (OPUS) SOLUTION (ALSO ATTACH THE OPUS REPORT),
 OR THE NAME OF THE REAL TIME NETWORK USED.
  
  