| 2021-10-29 10:25:59 | ELEVATION CERTIFICATE |
| | REVIEW COMMENTS |
| | 145 BLOOMFIELD DRIVE |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) CORRECTED. |
| | |
| | 2) CORRECTED. |
| | |
| | 3) CORRECTED. |
| | |
| | 4) [THIS INFORMATION WAS ENTERED IN THE WRONG LOCATION. |
| | THE FLOOD OPENINGS ARE LOCATED IN THE ATTACHED GARAGE, |
| | WHICH IS ITEM A9.] THERE ARE (4) FLOOD OPENINGS |
| | SPECIFIED ON THE PLANS AND SHOWN IN THE PHOTOGRAPHS. |
| | ITEM A9 B) LISTS 0. |
| | |
| | 5) [THIS INFORMATION WAS ENTERED IN THE WRONG LOCATION. |
| | THE FLOOD OPENINGS ARE LOCATED IN THE ATTACHED GARAGE, |
| | WHICH IS ITEM A9. THE PRODUCT EVALUATIONS THAT WERE |
| | SUBMITTED ARE FOR SMART VENTS. THE INFORMATION FOR THE |
| | SMART VENTS NEEDS TO BE PROVIDED RATHER THAN THE |
| | CALCULATIONS FOR THE GREENHECK LOUVERS SHOWN ON THE |
| | ORIGINAL BUILDING PLANS. THE FLOOD OPENINGS ARE |
| | REQUIRED TO BE LOCATED NO HIGHER THAN 1.0 FOOT ABOVE |
| | THE HIGHER OF THE EXTERIOR OR INTERIOR GRADE OR FLOOR |
| | IMMEDIATELY BELOW THE OPENING. IF THE INTERIOR GRADE |
| | ELEVATION IS USED, NOTE THIS IN THE COMMENTS AREA OF |
| | SECTION D. IT SHOULD ALSO BE NOTED IN THE COMMENTS AREA |
| | OF SECTION D THAT ENGINEERED SMART VENTS ARE INSTALLED. |
| | ] A9 C) LISTS THE NET AREA OF FLOOD OPENINGS AS 0.0 |
| | SQIN. SHEET A-1.0 OF THE PLANS HAS CALCULATIONS |
| | SPECIFYING THAT 7448 SQIN OF NET OPENING AREA WILL BE |
| | PROVIDED. |
| | |
| | 6) CORRECTED. |
| | |
| | 7) CORRECTED. |
| | |
| | 8) CORRECTED. |
| | |
| | 9) CORRECTED. |
| | |
| | 10) CORRECTED. |
| | |
| | 11) [ VERIFY THE CORRECT ELEVATION AND SPECIFY IT ON |
| | BOTH DOCUMENTS. ] ITEM C2 D) LISTS THE ELEVATION FOR |
| | THE TOP OF GARAGE SLAB AS 6.6 FT. THE TIE IN SURVEY |
| | SPECIFIES THE GARAGE ELEVATION AS 6.21' FT. THESE |
| | ELEVATIONS NEED TO BE CONSISTENT. |
| | |
| | 12) [ THE EQUIPMENT WILL HAVE TO BE RAISED SO THAT IT |
| | IS ABOVE THE DFE WHICH IS 8.0' NAVD. ] ITEM C2 E) LISTS |
| | THE LOWEST ELEVATION OF THE EQUIPMENT SERVICING THE |
| | BUILDING AS 7.5 FT. THE EQUIPMENT IS REQUIRED TO BE AT |
| | OR ABOVE THE DFE WHICH IS 8' NAVD. |
| | |
| | 13) [ ENTER THIS INFORMATION IN THE COMMENTS AREA OF |
| | SECTION D. ] THE METHOD USED TO DETERMINE LATITUDE AND |
| | LONGITUDE IS TO BE INDICATED IN THE COMMENTS AREA OF |
| | SECTION D. |
| | |
| | 14) [ THE PRODUCT APPROVAL/EVALUATION IS FOR SMART VENT |
| | ENGINEERED FLOOD VENTS. THESE ARE NOT THE ONES THAT ARE |
| | SPECIFIED ON THE PLANS. THE PLANS WILL NEED TO BE |
| | REVISED TO SHOW THE SMART VENTS AND THEIR LOCATIONS. ] |
| | SUBMIT THE SPECIFICATIONS, EVALUATION REPORT, PRODUCT |
| | APPROVAL, ETC. FOR THE FLOOD OPENINGS THAT WERE USED. |
| | THE PHOTOS APPEAR TO SHOW DIFFERENT FLOOD VENTS THAN |
| | THE GREENHECK LOUVERS THAT ARE SPECIFIED ON THE PLANS. |
| | |
| | 15) [ PHOTOS OF ELEVATIONS SHOWING THE FLOOD OPENINGS |
| | ARE REQUIRED. ] NEW PHOTOS OF THE BUILDING SHOWING THE |
| | FINISH GRADES ARE REQUIRED. |
| | |
| | 16) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | 17) NEW COMMENT. THE BUILDING OWNER'S NAME IN ITEM A1 |
| | IS 145 BLOOMFIELD TRUST. THE CITY'S AND PROPERTY |
| | APPRAISER'S RECORD HAVE THE OWNER AS PAMELA LOMBA. |
| | PLEASE CORRECT. |
| | |
| | 18) NEW COMMENT. ITEM C2 HAS GPS FOR BENCHMARK |
| | UTILIZED. FEMA'S EC INSTRUCTIONS STATE THAT FOR A GPS |
| | SURVEY, INDICATE THE BENCHMARK USED FOR THE BASE |
| | STATION, THE CONTINUOUSLY OPERATING REFERENCE STATIONS |
| | (CORS) SITES USED FOR AN ON-LINE POSITIONING USER |
| | SERVICE (OPUS) SOLUTION (ALSO ATTACH THE OPUS REPORT), |
| | OR THE NAME OF THE REAL TIME NETWORK USED. |
| | |
| | |