Plan Review Notes
Plan Review Notes For Permit 21100717
Permit Number 21100717
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-26 11:04:21ELEVATION CERTIFICATE
 REVIEW COMMENTS
 145 BLOOMFIELD DRIVE
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LATITUDE AND LONGITUDE FOR ITEM A5 ARE INCORRECT
 AND ARE REQUIRED TO BE AT LEAST 5 DECIMAL PLACES.
 CHANGE TO LATITUDE 26.65871 AND LONGITUDE -80.04876.
  
 2) FOR ITEM A7 THE BUILDING DIAGRAM NUMBER SHOULD BE 1B
 FOR A RAISED SLAB ON GRADE.
  
 3) THE PLANS SPECIFY THE ATTACHED GARAGE IS 535 SQFT.
 ITEM A9 A) HAS 500 SQFT.
  
 4) THERE ARE (4) FLOOD OPENINGS SPECIFIED ON THE PLANS
 AND SHOWN IN THE PHOTOGRAPHS. ITEM A9 B) LISTS 0.
  
 5) A9 C) LISTS THE NET AREA OF FLOOD OPENINGS AS 0.0
 SQIN. SHEET A-1.0 OF THE PLANS HAS CALCULATIONS
 SPECIFYING THAT 7448 SQIN OF NET OPENING AREA WILL BE
 PROVIDED.
  
 6) IN ITEM B3 THE 2-LETTER STATE ABBREVIATION SHOULD BE
 ENTERED. FLORIDA SHOULD NOT BE SPELLED OUT.
  
 7) THE DATE OF THE FIRM IN ITEM B6 IS INCORRECT. THE
 CORRECT DATE IS 10-05-2017.
  
 8) THE EFFECTIVE DATE OF THE FIRM PANEL IN ITEM B7 IS
 ALSO INCORRECT. THE CORRECT DATE IS 10-05-2017.
  
 9) THE FLOOD ZONES IN B8 SHOULD BE X500 & AE.
  
 10) FINISHED CONSTRUCTION IS MARKED IN ITEM C1. THE
 PHOTOS DO NOT APPEAR TO SHOW THAT THE GRADING AROUND
 THE BUILDING IS COMPLETE WHICH IS REQUIRED FOR THE
 FINAL E. C.
  
 11) ITEM C2 D) LISTS THE ELEVATION FOR THE TOP OF
 GARAGE SLAB AS 6.6 FT. THE TIE IN SURVEY SPECIFIES THE
 GARAGE ELEVATION AS 6.21' FT. THESE ELEVATIONS NEED TO
 BE CONSISTENT.
  
 12) ITEM C2 E) LISTS THE LOWEST ELEVATION OF THE
 EQUIPMENT SERVICING THE BUILDING AS 7.5 FT. THE
 EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE DFE WHICH
 IS 8' NAVD.
  
 13) THE METHOD USED TO DETERMINE LATITUDE AND LONGITUDE
 IS TO BE INDICATED IN THE COMMENTS AREA OF SECTION D.
  
 14) SUBMIT THE SPECIFICATIONS, EVALUATION REPORT,
 PRODUCT APPROVAL, ETC. FOR THE FLOOD OPENINGS THAT WERE
 USED. THE PHOTOS APPEAR TO SHOW DIFFERENT FLOOD VENTS
 THAN THE GREENHECK LOUVERS THAT ARE SPECIFIED ON THE
 PLANS.
  
 15) NEW PHOTOS OF THE BUILDING SHOWING THE FINISH
 GRADES ARE REQUIRED.
  
 16) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  