2022-01-03 08:29:262ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21100715
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS A NOTE ON THE MECHANICAL DRAWING STATING?
 THESE DRAWINGS ARE FOR INTERIM REVIEW AND ARE NOT
 INTENDED FOR REGULATORY APPROVAL, PERMITTING, OR
 CONSTRUCTION PURPOSES. PLEASE SUBMIT A MECHANICAL
 DRAWING THAT IS SIGNED BY THE DESIGNER. FS 471,481
  
 2) IS THIS A LIKE FOR LIKE CHANGE OUT FOR THIS PROJECT?
 IF SO PLEASE SUBMIT THE LIKE FOR LIKE FORMS THAT SHOWS
 THE EXISTING UNITS AND THE NEW UNITS.
  
 3) IF THIS IS NOT A LIKE FOR LIKE CHANGE OUT PLEASE
 SUBMIT THE PREVIOUSLY REQUESTED ENERGY CALCULATIONS AND
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC
 107.2.1
  
 4) PLEASE SHOW THE APPLIANCE ANCHORAGE FOR THE CU?S.
 FBC RES M1307.2
  
 5) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND
 TERMINATION LOCATION. FBC RES M1411.3
  
 6) DOES THE KITCHEN STOVE HAVE A HOOD ABOVE? IF SO IS
 IT DUCTED TO THE EXTERIOR? IF IT DOES HAVE A FAN DUCTED
 TO THE EXTERIOR WHAT IS THE CFM OF THE EXHAUST? PLEASE
 SHOW THE HOOD ON THE DRAWINGS ALONG WITH THE DUCT. FBC
 RES M1503.4
  
 7) PLEASE SHOW THE ACCESS FOR THE UNIT IN THE GARAGE,
 IT ISN?T CLEAR IF THE LOCATION OF THIS UNIT IS IN AN
 ATTIC OR SUSPENDED FROM THE CEILING OF THE GARAGE. FBC
 RES M1305.1.3
  
 8) PLEASE EXPLAIN, IS THE AHU-2 LOCATED IN THE STORAGE
 CLOSET OR THE ATTIC? IF IT IS LOCATED IN THE ATTIC
 PLEASE SHOW THE ACCESS FOR THIS UNIT. FBC RES M1305.1.3
  
 9) PLEASE SHOW THE DRYER EXHAUST AND OUTDOOR
 TERMINATION LOCATION.
  
 10) PLEASE SHOW THAT THE BATH EXHAUST TERMINATION
 LOCATION IS A MINIMUM OF 3 FEET FROM ANY OPERABLE
 OPENING INTO THE STRUCTURE. FBC RES M1501.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  