| 2022-01-03 08:29:26 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21100715 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE IS A NOTE ON THE MECHANICAL DRAWING STATING? |
| | THESE DRAWINGS ARE FOR INTERIM REVIEW AND ARE NOT |
| | INTENDED FOR REGULATORY APPROVAL, PERMITTING, OR |
| | CONSTRUCTION PURPOSES. PLEASE SUBMIT A MECHANICAL |
| | DRAWING THAT IS SIGNED BY THE DESIGNER. FS 471,481 |
| | |
| | 2) IS THIS A LIKE FOR LIKE CHANGE OUT FOR THIS PROJECT? |
| | IF SO PLEASE SUBMIT THE LIKE FOR LIKE FORMS THAT SHOWS |
| | THE EXISTING UNITS AND THE NEW UNITS. |
| | |
| | 3) IF THIS IS NOT A LIKE FOR LIKE CHANGE OUT PLEASE |
| | SUBMIT THE PREVIOUSLY REQUESTED ENERGY CALCULATIONS AND |
| | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC |
| | 107.2.1 |
| | |
| | 4) PLEASE SHOW THE APPLIANCE ANCHORAGE FOR THE CU?S. |
| | FBC RES M1307.2 |
| | |
| | 5) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND |
| | TERMINATION LOCATION. FBC RES M1411.3 |
| | |
| | 6) DOES THE KITCHEN STOVE HAVE A HOOD ABOVE? IF SO IS |
| | IT DUCTED TO THE EXTERIOR? IF IT DOES HAVE A FAN DUCTED |
| | TO THE EXTERIOR WHAT IS THE CFM OF THE EXHAUST? PLEASE |
| | SHOW THE HOOD ON THE DRAWINGS ALONG WITH THE DUCT. FBC |
| | RES M1503.4 |
| | |
| | 7) PLEASE SHOW THE ACCESS FOR THE UNIT IN THE GARAGE, |
| | IT ISN?T CLEAR IF THE LOCATION OF THIS UNIT IS IN AN |
| | ATTIC OR SUSPENDED FROM THE CEILING OF THE GARAGE. FBC |
| | RES M1305.1.3 |
| | |
| | 8) PLEASE EXPLAIN, IS THE AHU-2 LOCATED IN THE STORAGE |
| | CLOSET OR THE ATTIC? IF IT IS LOCATED IN THE ATTIC |
| | PLEASE SHOW THE ACCESS FOR THIS UNIT. FBC RES M1305.1.3 |
| | |
| | 9) PLEASE SHOW THE DRYER EXHAUST AND OUTDOOR |
| | TERMINATION LOCATION. |
| | |
| | 10) PLEASE SHOW THAT THE BATH EXHAUST TERMINATION |
| | LOCATION IS A MINIMUM OF 3 FEET FROM ANY OPERABLE |
| | OPENING INTO THE STRUCTURE. FBC RES M1501.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |