Plan Review Notes
Plan Review Notes For Permit 21100715
Permit Number 21100715
Review Stop E
Sequence Number 2
Notes
Date Text
2022-01-05 15:08:11ELECTRICAL REVIEW FAILED
 1) PLEASE DETAIL SMOKE DETECTORS AS CARBON MONOXIDE FBC
 R315.1
 2) ENSURE CLOSET LIGHTS TO COMPLY WITH NEC NEC.16. A
 NOTE WILL SUFFICE
 3) DETAIL KITCHEN ISLAND RECEPTACLES AS PER NEC
 210.529(C)(2)
 4) WASHER, DRYER, A/C 1, AC2, MASTER BATH RECEPTACLES,
 MASTER BEDROOM RECEPTACLES, UPSTAIRS BEDROOM
 RECEPTACLES, RANGE WIRING, BALCONY, GUEST BATH
 RECEPTACLES, FRONT AND REAR OUTSIDE PATIO RECEPTACLES,
 NOT SHOWN. IF ANY WIRING IS EXISTING, PLEASE DETAIL.
 FBC 107.2
 5) ENSURE TAMPER RESISTANT RECEPTACLES WILL BE USED TO
 COMPLY WITH NEC 406.13. A NOTE WILL SUFFICE
 6) ENSURE 120-VOLT CIRCUITS COMPLY WITH ARC FAULT
 REQUIREMENTS AS PER NEC 210.12. A NOTE WILL SUFFICE
 7) PROVIDE A NOTE POOL IS SEPARATE PERMIT
 8) PROVIDE A CORRECTED LOAD CALCULATION USING ALL
 ELECTRICAL LOADS AS OUTLINED IN NEC 220.80
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  