| 2022-01-05 15:08:11 | ELECTRICAL REVIEW FAILED |
| | 1) PLEASE DETAIL SMOKE DETECTORS AS CARBON MONOXIDE FBC |
| | R315.1 |
| | 2) ENSURE CLOSET LIGHTS TO COMPLY WITH NEC NEC.16. A |
| | NOTE WILL SUFFICE |
| | 3) DETAIL KITCHEN ISLAND RECEPTACLES AS PER NEC |
| | 210.529(C)(2) |
| | 4) WASHER, DRYER, A/C 1, AC2, MASTER BATH RECEPTACLES, |
| | MASTER BEDROOM RECEPTACLES, UPSTAIRS BEDROOM |
| | RECEPTACLES, RANGE WIRING, BALCONY, GUEST BATH |
| | RECEPTACLES, FRONT AND REAR OUTSIDE PATIO RECEPTACLES, |
| | NOT SHOWN. IF ANY WIRING IS EXISTING, PLEASE DETAIL. |
| | FBC 107.2 |
| | 5) ENSURE TAMPER RESISTANT RECEPTACLES WILL BE USED TO |
| | COMPLY WITH NEC 406.13. A NOTE WILL SUFFICE |
| | 6) ENSURE 120-VOLT CIRCUITS COMPLY WITH ARC FAULT |
| | REQUIREMENTS AS PER NEC 210.12. A NOTE WILL SUFFICE |
| | 7) PROVIDE A NOTE POOL IS SEPARATE PERMIT |
| | 8) PROVIDE A CORRECTED LOAD CALCULATION USING ALL |
| | ELECTRICAL LOADS AS OUTLINED IN NEC 220.80 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |