2022-04-05 14:35:031ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21100714
 4/5/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: CLARIFY IF THE GAS WATER HEATER IS NEW,
 EXISTING, OR A REPLACEMENT IN THE SAME LOCATION. PLEASE
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN INDICATING
 THE MAKE AND MODEL, BTUH LOAD, AND EFFICIENCY RATING-
 TABLE C404.2 FBC EC. COMMENT LISTED BELOW WILL APPLY TO
 NEW INSTALLATIONS:
 A) PROVIDE A DETAIL SHOWING THE INSTALLATION LOCATION
 AND REQUIRED CLEARANCES AS RECOMMENDED BY THE
 MANUFACTURER- SECTIONS G2406.1 & G2448.1 FBC RES.
 B) PROVIDE A GAS RISER DRAWING- SEC. 107.3.5.3 WPB.
 C) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SEC. G2407.1 FBC RES.
 D) PROVIDE A VENTING PLAN- SEC. G2426.2, G2426.7 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  