Plan Review Notes
Plan Review Notes For Permit 21100714
Permit Number 21100714
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-18 08:36:22BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED
 AT THIS TIME: ONLY STRUCTURAL PLANS SUBMITTED FOR
 REVIEW.
  
 1. PROVIDE ARCHITECTURAL PLANS. INCLUDE THE FOLLOWING
 INFORMATION:
 PROVIDE PROJECT DATA/DESIGN PARAMETERS:
 PROJECT DATA: 1&2 FAMILY DWELLING UNIT
  OCCUPANCY CLASSIFICATION R3 SFR
  SCOPE OF WORK
 DESIGN PARAMETERS: 2020 FBC EXISTING BUILDING
  2020 FBC RESIDENTIAL
  2017 NEC
 CLASSIFICATION OF WORK: ADDITION
 BUILDING CLASSIFICATION: VB
 EXPOSURE CLASSIFICATION: (B/C/D)?
 RISK CATEGORY: II
 MEAN ROOF HEIGHT:
 EXISTING UNDER AIR: /SF
 EXISTING COVERED: /SF
 NEW UNDER AIR: /SF
 NEW COVERED: /SF
 TOTALS: UNDER AIR /SF
  COVERED /SF
  
  
 2. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY
 LOCATION OF WORK.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDARY LINE SURVEY.
  
  
 3. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 5. PROVIDE A WINDOW AND DOOR SCHEDULE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. PROVIDE ENERGY CALC'S.
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1.SECTIONS R401 THROUGH R404.
 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED ?MANDATORY.?
 3. AN ENERGY RATING INDEX (ERI) APPROACH IN SECTION
 R406. *MUST BE PREPARED BY A 3RD PARTY*
 R401.3ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
  
 7. IDENTIFY CEILING AND WALL R-VALUE ON PLANS.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE
 ALTERNATIVE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  