| Date |
Text |
| 2021-12-18 08:36:22 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED |
| | AT THIS TIME: ONLY STRUCTURAL PLANS SUBMITTED FOR |
| | REVIEW. |
| | |
| | 1. PROVIDE ARCHITECTURAL PLANS. INCLUDE THE FOLLOWING |
| | INFORMATION: |
| | PROVIDE PROJECT DATA/DESIGN PARAMETERS: |
| | PROJECT DATA: 1&2 FAMILY DWELLING UNIT |
| | OCCUPANCY CLASSIFICATION R3 SFR |
| | SCOPE OF WORK |
| | DESIGN PARAMETERS: 2020 FBC EXISTING BUILDING |
| | 2020 FBC RESIDENTIAL |
| | 2017 NEC |
| | CLASSIFICATION OF WORK: ADDITION |
| | BUILDING CLASSIFICATION: VB |
| | EXPOSURE CLASSIFICATION: (B/C/D)? |
| | RISK CATEGORY: II |
| | MEAN ROOF HEIGHT: |
| | EXISTING UNDER AIR: /SF |
| | EXISTING COVERED: /SF |
| | NEW UNDER AIR: /SF |
| | NEW COVERED: /SF |
| | TOTALS: UNDER AIR /SF |
| | COVERED /SF |
| | |
| | |
| | 2. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY |
| | LOCATION OF WORK. |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE |
| | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| | ACCURATE AND INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | |
| | 3. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED BOUNDARY LINE SURVEY. |
| | FBC R401.3 SITE DRAINAGE |
| | |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. |
| | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES WITHIN THE FIRST 10 FEET. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 5. PROVIDE A WINDOW AND DOOR SCHEDULE. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 6. PROVIDE ENERGY CALC'S. |
| | R401.2COMPLIANCE. |
| | PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | 1.SECTIONS R401 THROUGH R404. |
| | 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401 |
| | THROUGH R404 LABELED ?MANDATORY.? |
| | 3. AN ENERGY RATING INDEX (ERI) APPROACH IN SECTION |
| | R406. *MUST BE PREPARED BY A 3RD PARTY* |
| | R401.3ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| | (MANDATORY). |
| | |
| | 7. IDENTIFY CEILING AND WALL R-VALUE ON PLANS. |
| | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| | STORIES. |
| | FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE |
| | ALTERNATIVE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |