| Notes |
| Date |
Text |
| 2022-02-04 15:51:22 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 1603.1 & 1609, PLEASE PROVIDE THE DESIGN | | | WINDLOADS (SIGNED/SEALED)FOR THE PROPOSED | | | OPENING/OPENINGS TO RECEIVE SHUTTERS. | | | | | | THE SUBMITTED ENGINEER'S LETTER CLARIFIES THE LOCATIONS | | | FOR ZONE 4 AND ZONE 5 BUT NOT THE WINDLOAD DESIGN | | | PRESSURES FOR THE OPENING/OPENINGS. | | | THE PLAN SHEET THAT WAS LABELED AS "BROWARD WINDLOAD | | | CHART FBC 2020" WAS CANCELLED OUT AS THAT CHART WAS FOR | | | BROWARD COUNTY NOT THIS LOCATION, THE MEAN ROOF HEIGHT | | | WAS NOT CORRECT AS THIS IS A HIGH RISE, AND THE DESIGN | | | PROFESSIONAL NEEDS TO SIGN AND SEAL THE DOCUMENT. | | | |
|