| 2021-12-15 08:39:02 | FLOORING REVISION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE TYPE OF |
| | FLOORING AND THE LOCATION OF THE FLOORING - ALSO SHOW |
| | THE SQUARE FOOTAGE FOR EACH FLOORING TYPE. |
| | |
| | 2) PLEASE SHOW THE ADDITIONAL JOB VALUE ON THE PLAN |
| | REVIEW REQUEST FORM IN THE SPACE PROVIDED. |
| | |
| | 3) ACUSTICAL TEST REPORT PROVIDED FOR "MAXXIM SIM 90 |
| | UNDERLAYMENT" AND "PROFLEX SSC 70" SHOWS A DROP CEILING |
| | - TEST REPORT CANNOT INCLUDE A DROP CEILING UNLESS THE |
| | DROP CEILING DESCRIPTION MATCHES YOUR CEILING. |
| | |
| | 4) PLEASE PROVIDE A FLAME SPREAD TEST REPORT FOR THE |
| | WOOD FLOORING - FBC 603.1, ALLOWABLE MATERIALS IN NON |
| | COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2, |
| | ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN |
| | ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5) YOU HAVE A FEW DIFFERENT FLOORING UNDERLAYMENTS IN |
| | PROJECTDOX - ON THE FLOOR PLAN THAT YOU NEED TO PROVIDE |
| | WRITE THE UNDERLAYMENT NAMES TO BE USED SO THAT I DON'T |
| | KEEP FAILING THE REVIEW FOR THE SAME DOCUMENTS |
| | PROVIDED. I WILL REMOVE THE TEST REPORTS FROM |
| | PROJECTDOX THAT ARE NOT WRITTEN ON THE FLOOR PLAN. |