Plan Review Notes
Plan Review Notes For Permit 21100680
Permit Number 21100680
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-01 15:06:50FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PROFLEX SSC 70 = CANNOT USE A TEST REPORT THAT
 INCLUDES A DROP CEILING UNLESS THE UNIT BELOW YOU HAS A
 DROP CEILING AND INSULATION THAT MATCHES THE TEST
 REPORT GIVEN.
  
 2) YOU WILL ALSO NEED TO PROVIDE A FLAME SPREAD TEST
 REPORT FOR THE PROFLEX SSC 70 ITSELF OR A TILE AND
 UNDERLAYMENT SYSTEM - FBC 603.1, ALLOWABLE MATERIALS IN
 NON COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2,
 ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.