| Plan Review Notes For Permit 21100680 |
| Permit Number |
21100680 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-01 15:06:50 | FLOORING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PROFLEX SSC 70 = CANNOT USE A TEST REPORT THAT | | | INCLUDES A DROP CEILING UNLESS THE UNIT BELOW YOU HAS A | | | DROP CEILING AND INSULATION THAT MATCHES THE TEST | | | REPORT GIVEN. | | | | | | 2) YOU WILL ALSO NEED TO PROVIDE A FLAME SPREAD TEST | | | REPORT FOR THE PROFLEX SSC 70 ITSELF OR A TILE AND | | | UNDERLAYMENT SYSTEM - FBC 603.1, ALLOWABLE MATERIALS IN | | | NON COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2, | | | ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED | | | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE | | | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT | | | MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN | | | ACCORDANCE WITH ASTM E 84 OR UL 723. |
|