| 2022-08-16 15:37:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21100652 85 SOUTHERN BLVD |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | MOST COMMENTS FROM THE 1ST REVIEW COPIED BELOW WERE NOT |
| | ADDRESSED. NO CORRECTED PLANS HAVE BEEN PROVIDED FOR |
| | REVIEW. |
| | NEW COMMENT. IT APPEARS THAT PERMIT 21091249 AND THIS |
| | PERMIT 21100652 ARE FOR THE SAME PROJECT, ONE FOR |
| | MECHANICAL AND ONE FOR PLUMBING. THE SAME PLUMBING |
| | SCOPE HAS BEEN REVIEWED BY TWO (2) DIFFERENT PLANS |
| | EXAMINERS |
| | |
| | 1.GENERAL NOTE: DEFERRED SUBMITTALS FBC 107.3.4.1 |
| | REGARDING THE SUMP PUMP, POINT OF USE WATER HEATERS, |
| | ETC., DEFERRED SUBMITTALS IN THE FORM OF MANUFACTURERS |
| | SPECIFICATIONS/INSTALLATION INSTRUCTIONS MAY BE |
| | SUBMITTED IN ACCORDANCE WITH WPB FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL |
| | BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND |
| | ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | BY PROVIDING THE NOTE ABOVE ON THE CONSTRUCTION |
| | DOCUMENTS TO BE REVIEWED AND LISTING THE ITEMS TO BE |
| | DEFERRED, YOU MAY PROCEED IN THIS MANNER. |
| | ENGINEER DID NOT ADDRESS. SOME ITEMS WERE SUBMITTED IN |
| | SECOND REVIEW, SOME WERE NOT. |
| | |
| | 2.SECOND REQUEST:A REVIEW OF MINIMUM PLUMBING FIXTURE |
| | REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE |
| | PLUMBING REVIEW PROCESS BUT IS TYPICALLY ADDRESSED ON |
| | THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING THESE |
| | REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED PRIOR TO |
| | A PLUMBING REVIEW APPROVAL. |
| | THE RESTROOM DOES NOT APPEAR TO COMPLY WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6. PER WPB FBC 107.2.1, CLARIFY. |
| | PLEASE REVIEW FBC ACC 203.9, 213.1. PROVIDE ELEVATIONS |
| | AND PLAN VIEW SHOWING COMPLIANCE WITH FBC ACC AS |
| | FOLLOWS AND IS APPLICABLE. |
| | A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | E) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET PER FBC ACC 604.6 |
| | F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| | FBC ACC 604.4. |
| | H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT |
| | THE CENTER) OF THE GRIPPING SURFACE, |
| | I) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO THE |
| | ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED IN |
| | THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION |
| | FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER |
| | CLOSET. |
| | J)LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | K) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5 |
| | PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 |
| | PER FBC ACC 212.3. DOES NOT APPLY TO A SERVICE SINK. |
| | L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. |
| | M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. |
| | N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | O) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 OR |
| | 304.3.2. |
| | ENGINEER'S RESPONSE: RESTROOMS DO NOT NEED TO BE ADA |
| | COMPLIANT. WILL REVISE NOTES ON PLUMBING FIXTURE |
| | SCHEDULE. |
| | NOTES HAVE NOT BEEN REVISED, HOWEVER, ADA COMPLIANT |
| | FIXTURES MAY BE PROVIDED. |
| | |
| | 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | OCCUPANCY TYPE AND OCCUPANCY LOAD FOR STRUCTURE. |
| | PROVIDE FIXTURE SCHEDULE LISTING REQUIRED PLUMBING |
| | FIXTURES AND QUANTITIES REQUIRED BY FBC PL TABLE 403.1 |
| | TO ACCOMMODATE THE STATED OCCUPANCY AND OCCUPANCY LOAD. |
| | ENGINEER'S RESPONSE: CONCUR. THIS STRUCTURE WILL HAVE 1 |
| | STAFF MEMBER. WILL PROVIDE FIXTURE SCHEDULE LISTING |
| | REQUIRED PLUMBING FIXTURES AND QUANTITIES. |
| | OCCUPANCY TYPE AND LOAD HAVE NOT BEEN PROVIDED |
| | |
| | 4. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE AN |
| | OVERALL FLOOR PLAN FOR EACH LEVEL SHOWING RESPECTIVE |
| | LOCATIONS OF PIER 6 AND PIER 7 AS WELL AS COMPREHENSIVE |
| | ELEVATION VIEW(S) IDENTIFYING THE LEVELS. |
| | |
| | 5. SECOND REQUEST: MP-1: PER WPB FBC 107.2.1, SPECIFY A |
| | CARRIER SYSTEM FOR P-1 WATER CLOSET; PROVIDE |
| | MANUFACTURERS SPECIFICATION/INSTALLATION MANUAL FOR |
| | CARRIER SYSTEM FOR P-1 WATER CLOSET OR LIST AS A |
| | DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.1; |
| | SEE COMMENT #1. |
| | |
| | 7. SECOND REQUEST: MP-1: FIXTURE SCHEDULE P-4 SERVICE |
| | SINK; PER WPB FBC 107.2.1, PROVIDE SUMP PUMP AND BASIN |
| | DETAIL SHOWING PIPING AND VALVE ARRANGEMENT SHOWING |
| | COMPLIANCE WITH FBC PL SECTION 712. PER FBC PL 712.2, A |
| | CHECK VALVE AND A FULL OPEN VALVE SHALL BE LOCATED IN |
| | THE DISCHARGE LINE FROM THE SUMP AND SHALL BE |
| | ACCESSIBLE. |
| | |
| | 8. SECOND REQUEST: PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL FOR SUMP PUMP OR LIST |
| | AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC |
| | 107.3.4.1; SEE COMMENT #1. |
| | |
| | 9. SECOND REQUEST: MP-1: FIXTURE SCHEDULE P-4 SERVICE |
| | SINK; A VACUUM BREAKER IS REQUIRED ON THE FAUCET HOSE |
| | THREADS PER FBC PL 608.1 AND 608.2. PER WPB FBC |
| | 107.2.1, SPECIFY AND ADD TO P-4 DESCRIPTION. |
| | |
| | 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | TANKLESS WATER HEATER INSTALLATION DETAIL SHOWING |
| | PIPING AND VALVE ARRANGEMENT. |
| | |
| | 11. SECOND REQUEST: PROVIDE MANUFACTURE'RS |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE WATER HEATERS |
| | OR LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC |
| | 107.3.4.1; SEE COMMENT #1. |
| | NEW COMMENT: SEE MP-6/NOTE 9: CALLS FOR ELECTRIC |
| | TANKLESS WATER HEATER 4.1 KW/14.8 AMPS, COORDINATE |
| | VOLTAGE WITH ELECTRICAL INSTALLER. PER WPB FBC 107.2.1, |
| | PROVIDE MANUFACTURER AND MODEL FOR WATER HEATER; |
| | ADDITIONALLY, IT IS NOTED TO A PERMIT IS REQUIRED FOR |
| | ELECTRICAL WORK. THERE IS NO ELECTRICAL SCHEDULE. THERE |
| | ARE NO ELECTRICAL DRAWINGS. |
| | |
| | 12. SECOND REQUEST: MP-1: FIXTURE SCHEDULE P-2 |
| | LAVATORY; FBC PL 419.5 REQUIRES COLD OR TEMPERED WATER |
| | SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH |
| | FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED |
| | FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | A) PER WPB FBC 107.2.1, PLEASE CLARIFY IF THERE IS TO |
| | BE PUBLIC ACCESS TO THE RESTROOM. COMPLIANT TEMPERED |
| | WATER DEVICES MAY BE PROVIDED IN ANY CASE BUT SHALL BE |
| | PROVIDED IF PUBLIC. |
| | B) PER WPB FBC 107.2.1, A SPECIFICATION WOULD BE |
| | REQUIRED. |
| | ENGINEER RESPONSE: CONCUR. WILL SPECIFY A THERMOSTATIC |
| | MIXING VALVE FOR TEMPERED WATER TO SERVICE SINK. |
| | LAVATORY SHALL ONLY BE PROVIDED WITH COLD WATER. |
| | NEW COMMENT: REVISED(?) PLANS DO NOT REFLECT COLD WATER |
| | ONLY TO P-2 AND STILL SHOW A WATER HEATER |
| | |
| | 13. SECOND REQUEST: P-3 SINK AND P-4 SINK IN RISER |
| | BELOW P-2 LAVATORY, PER FBC PL 607.1, PROVIDE HOT |
| | WATER. |
| | ENGINEER RESPONSE: CONCUR. ELECTRIC WATER HEATER TO BE |
| | PROVIDED FOR SERVICE SINK ON MP-4. |
| | NEW COMMENT: REVISED(?) PLAN MP-8 DOES NOT REFLECT HOT |
| | WATER TO P-4 AND ELECTRIC WATER HEATER IS NOT SHOWN |
| | |
| | 14. SECOND REQUEST: PROVIDE DETAIL FOR HB-1 WALL BOX |
| | AND SHUTOFF VALVE. WILL WALL BOX BE RECESSED INTO |
| | STRUCTURE? |
| | |
| | 15. SECOND REQUEST: PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE WALL BOX OR |
| | LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC |
| | 107.3.4.1; SEE COMMENT #1. |
| | |
| | 16. SECOND REQUEST: MP-2: TAG NOTE 1: SUMP PIT AND PUMP |
| | BY OTHERS; PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SUMP |
| | PIT AND PUMP BY OTHERS SHOWING DIMENSIONS, PIPING AND |
| | VALVE ARRANGEMENT. COMPLY WITH FBC PL SECTION 712. PER |
| | FBC PL 712.2, A CHECK VALVE AND A FULL OPEN VALVE SHALL |
| | BE LOCATED IN THE DISCHARGE LINE FROM THE SUMP AND |
| | SHALL BE ACCESSIBLE. ADDITIONALLY, INDICATE THE PUMP |
| | DISCHARGE GPM SHOWING IT IS CAPABLE OF DISCHARGING THE |
| | COMBINED STORM WATER AND A/C CONDENSATE ENTERING THE |
| | PIT. |
| | |
| | 17. SECOND REQUEST: MP-2: TAG NOTE 4: REFERS TO B1-424 |
| | FOR ADDITIONAL INFORMATION. PER WPB FBC 107.2.1, |
| | PROVIDE REFERENCED DRAWING |
| | |
| | 18. SECOND REQUEST: MP-4: NOTE 3: PER FBC PL 607.1, |
| | PROVIDE HOT WATER AND COLD WATER |
| | |
| | 19. SECOND REQUEST: MP-4: NOTE 11: PER FBC PL 712.2, A |
| | CHECK VALVE AND A FULL OPEN VALVE SHALL BE LOCATED IN |
| | THE DISCHARGE LINE FROM THE SUMP AND SHALL BE |
| | ACCESSIBLE. |
| | |
| | 20. SECOND REQUEST: MP-4: NOTE 10: PROVIDE DETAIL(S) |
| | FOR UTILITIES CONNECTION(S) OR DISPOSAL POINTS |
| | |
| | 21. SECOND REQUEST: MP-4: PROVIDE NOTE FOR SUMP |
| | DISCHARGE CONNECTION TO BUILDING DRAIN "PER FBC PL |
| | 712.3.5, PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL |
| | CONNECT TO A BUILDING SEWER, BUILDING DRAIN, SOIL |
| | STACK, WASTE STACK OR HORIZONTAL BRANCH DRAIN. WHERE |
| | THE DISCHARGE LINE CONNECTS INTO HORIZONTAL DRAINAGE |
| | PIPING, THE CONNECTION SHALL BE MADE THROUGH A WYE |
| | FITTING INTO THE TOP OF THE DRAINAGE PIPING AND SUCH |
| | WYE FITTING SHALL BE LOCATED NOT LESS THAN 10 PIPE |
| | DIAMETERS FROM THE BASE OF ANY SOIL STACK, WASTE STACK |
| | OR FIXTURE DRAIN." |
| | |
| | 22. SECOND REQUEST: MP-5: NOTE 4; PER FBC PL 607.1, |
| | PROVIDE HOT WATER AND COLD WATER |
| | ENGINEER RESPONSE: CONCUR. ELECTRIC WATER HEATER TO BE |
| | PROVIDED FOR SERVICE SINK ON MP-4. |
| | NEW COMMENT: REVISED(?) PLAN MP-8 DOES NOT REFLECT HOT |
| | WATER TO P-4 AND ELECTRIC WATER HEATER IS NOT SHOWN |
| | |
| | 23. SECOND REQUEST: MP-6: ADD TO NOTE 8, "VENT |
| | TERMINALS EXTENDING THROUGH THE WALL SHALL COMPLY WITH |
| | FBC PL 903.6" |
| | |
| | 24. SECOND REQUEST: MP-8: STORM DRAIN PIPING AT FD; |
| | REPLACE P-TRAP WITH QUARTER BEND SWEEP. SEE FBC PL |
| | 1002.3, 1101.6 AND 1103.1 |
| | |
| | 25. SECOND REQUEST: MP-8: PROVIDE AN INDIVIDUAL VENT |
| | FOR P-4 SERVICE SINK. SHOW COMPLIANCE WITH FBC PL 909.1 |
| | AND 1002.3(5) |
| | |
| | 26. SECOND REQUEST: MP-8: P-1 WATER CLOSET IS A WALL |
| | HUNG FIXTURE. PER WPB FBC 107.2.1, SHOW IN THE SANITARY |
| | RISER AS ABOVE FLOOR WALL CONNECTION. |
| | |
| | 27. SECOND REQUEST: MP-8: STORM RISER; PER WPB FBC |
| | 107.2.1, INCLUDE STORM DISCHARGE PIPING FROM SUMP. |
| | |
| | 28. SECOND REQUEST: MP-8: PROVIDE NOTE FOR PUMP |
| | DISCHARGE CONNECTION TO BUILDING DRAIN "PER FBC PL |
| | 712.3.5, PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL |
| | CONNECT TO A BUILDING SEWER, BUILDING DRAIN, SOIL |
| | STACK, WASTE STACK OR HORIZONTAL BRANCH DRAIN. WHERE |
| | THE DISCHARGE LINE CONNECTS INTO HORIZONTAL DRAINAGE |
| | PIPING, THE CONNECTION SHALL BE MADE THROUGH A WYE |
| | FITTING INTO THE TOP OF THE DRAINAGE PIPING AND SUCH |
| | WYE FITTING SHALL BE LOCATED NOT LESS THAN 10 PIPE |
| | DIAMETERS FROM THE BASE OF ANY SOIL STACK, WASTE STACK |
| | OR FIXTURE DRAIN." |
| | |
| | 29. SECOND REQUEST: MP-8: PROVIDE HOT WATER ROUTING OR |
| | TANKLESS WATER HEATERS FOR P-3, P-4 IN WATER RISER |
| | BELOW P-2. IF PROVIDING ROUTING, SPECIFY TANKLESS |
| | HEATER THAT WILL ACCOMMODATE P-2, P-3 AND P-4. |
| | |
| | 30. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPE |
| | HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE |
| | SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE |
| | 308.5." |
| | |
| | 31. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPING |
| | MATERIAL SPEC FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, |
| | FITTINGS AND JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, |
| | 7, 9 AND 11. |
| | A) ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | B) DISCHARGE PIPING FROM SUMP PUMPS SHALL BE PRESSURE |
| | RATED IN ACCORDANCE WITH FBC PL SECTIONS 712.3.3.1 AND |
| | 712.3.3.2, PROVIDE NOTE ON PLANS STATING THE SAME. |
| | |
| | 32. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | SPECIFICATION FOR 1) HOT WATER PIPING INSULATION AND 2) |
| | CONDENSATE PIPING INSULATION |
| | |
| | 33. SECOND REQUEST: MORE INFORMATION IS REQUIRED |
| | REGARDING THE STORM DRAIN. WHAT IS THE PURPOSE? IS THIS |
| | IN AN OPEN AREA SUBJECT TO RAINFALL? |
| | A) PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE |
| | CALCULATIONS FOR SIZING THE GRAVITY DRAIN COMPLYING |
| | WITH FBC PL TABLES 1106.2 AND 1106.3. |
| | B) NOTE THE REQUIRED SLOPE FOR THE HORIZONTAL PIPING. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |