| 2022-01-04 17:10:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21100652 401 CLEMATIS ST |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: |
| | 1.GENERAL NOTE: DEFERRED SUBMITTALS FBC 107.3.4.1 |
| | REGARDING THE SUMP PUMP, POINT OF USE WATER HEATERS, |
| | ETC., DEFERRED SUBMITTALS IN THE FORM OF MANUFACTURERS |
| | SPECIFICATIONS/INSTALLATION INSTRUCTIONS MAY BE |
| | SUBMITTED IN ACCORDANCE WITH WPB FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL |
| | BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND |
| | ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | BY PROVIDING THE NOTE ABOVE ON THE CONSTRUCTION |
| | DOCUMENTS TO BE REVIEWED AND LISTING THE ITEMS TO BE |
| | DEFERRED, YOU MAY PROCEED IN THIS MANNER. |
| | |
| | 2.A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | THE RESTROOM DOES NOT APPEAR TO COMPLY WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6. PER WPB FBC 107.2.1, CLARIFY. |
| | PLEASE REVIEW FBC ACC 203.9, 213.1. PROVIDE ELEVATIONS |
| | AND PLAN VIEW SHOWING COMPLIANCE WITH FBC ACC AS |
| | FOLLOWS AND IS APPLICABLE. |
| | ?A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | ?B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | ?C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | ?D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | ?E) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET PER FBC ACC 604.6 |
| | ?F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | ?G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| | FBC ACC 604.4. |
| | ?H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN |
| | A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT |
| | THE CENTER) OF THE GRIPPING SURFACE, |
| | ?I) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO |
| | THE ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED |
| | IN THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION |
| | FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER |
| | CLOSET. |
| | ?J)LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | ?K) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5 |
| | PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 |
| | PER FBC ACC 212.3. DOES NOT APPLY TO A SERVICE SINK. |
| | ?L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. |
| | ?M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. |
| | ?N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | ?O) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 |
| | OR 304.3.2. |
| | |
| | 3.PER WPB FBC 107.2.1, PROVIDE OCCUPANCY TYPE AND |
| | OCCUPANCY LOAD FOR STRUCTURE. PROVIDE FIXTURE SCHEDULE |
| | LISTING REQUIRED PLUMBING FIXTURES AND QUANTITIES |
| | REQUIRED BY FBC PL TABLE 403.1 TO ACCOMMODATE THE |
| | STATED OCCUPANCY AND OCCUPANCY LOAD. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE AN OVERALL FLOOR PLAN |
| | FOR EACH LEVEL SHOWING RESPECTIVE LOCATIONS OF PIER 6 |
| | AND PIER 7 AS WELL AS COMPREHENSIVE ELEVATION VIEW(S) |
| | IDENTIFYING THE LEVELS. |
| | |
| | 5. MP-1: PER WPB FBC 107.2.1, SPECIFY A CARRIER SYSTEM |
| | FOR P-1 WATER CLOSET; PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL FOR CARRIER SYSTEM |
| | FOR P-1 WATER CLOSET OR LIST AS A DEFERRED SUBMITTAL IN |
| | ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL FOR CARRIER FOR P-2 |
| | LAVATORY OR LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE |
| | WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 7. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; PER WPB FBC |
| | 107.2.1, PROVIDE SUMP PUMP AND BASIN DETAIL SHOWING |
| | PIPING AND VALVE ARRANGEMENT SHOWING COMPLIANCE WITH |
| | FBC PL SECTION 712. PER FBC PL 712.2, A CHECK VALVE AND |
| | A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE |
| | LINE FROM THE SUMP AND SHALL BE ACCESSIBLE. |
| | |
| | 8. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR SUMP PUMP OR LIST AS A DEFERRED SUBMITTAL IN |
| | ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 9. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; A VACUUM |
| | BREAKER IS REQUIRED ON THE FAUCET HOSE THREADS PER FBC |
| | PL 608.1 AND 608.2. PER WPB FBC 107.2.1, SPECIFY AND |
| | ADD TO P-4 DESCRIPTION. |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE TANKLESS WATER HEATER |
| | INSTALLATION DETAIL SHOWING PIPING AND VALVE |
| | ARRANGEMENT. |
| | |
| | 11. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE WATER HEATERS OR LIST AS A DEFERRED |
| | SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT |
| | #1. |
| | |
| | 12. MP-1: FIXTURE SCHEDULE P-2 LAVATORY; FBC PL 419.5 |
| | REQUIRES COLD OR TEMPERED WATER SHALL BE DELIVERED FROM |
| | LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC |
| | TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. |
| | ?A) PER WPB FBC 107.2.1, PLEASE CLARIFY IF THERE IS TO |
| | BE PUBLIC ACCESS TO THE RESTROOM. COMPLIANT TEMPERED |
| | WATER DEVICES MAY BE PROVIDED IN ANY CASE BUT SHALL BE |
| | PROVIDED IF PUBLIC. |
| | ?B) PER WPB FBC 107.2.1, A SPECIFICATION WOULD BE |
| | REQUIRED. |
| | |
| | 13. P-3 SINK AND P-4 SINK IN RISER BELOW P-2 LAVATORY, |
| | PER FBC PL 607.1, PROVIDE HOT WATER. |
| | |
| | 14. PROVIDE DETAIL FOR HB-1 WALL BOX AND SHUTOFF VALVE. |
| | WILL WALL BOX BE RECESSED INTO STRUCTURE? |
| | |
| | 15. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE WALL BOX OR LIST AS A DEFERRED SUBMITTAL |
| | IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 16. MP-2: TAG NOTE 1: SUMP PIT AND PUMP BY OTHERS; PER |
| | WPB FBC 107.2.1, PROVIDE DETAIL FOR SUMP PIT AND PUMP |
| | BY OTHERS SHOWING DIMENSIONS, PIPING AND VALVE |
| | ARRANGEMENT. COMPLY WITH FBC PL SECTION 712. PER FBC PL |
| | 712.2, A CHECK VALVE AND A FULL OPEN VALVE SHALL BE |
| | LOCATED IN THE DISCHARGE LINE FROM THE SUMP AND SHALL |
| | BE ACCESSIBLE. ADDITIONALLY, INDICATE THE PUMP |
| | DISCHARGE GPM SHOWING IT IS CAPABLE OF DISCHARGING THE |
| | COMBINED STORM WATER AND A/C CONDENSATE ENTERING THE |
| | PIT. |
| | |
| | 17. MP-2: TAG NOTE 4: REFERS TO B1-424 FOR ADDITIONAL |
| | INFORMATION. PER WPB FBC 107.2.1, PROVIDE REFERENCED |
| | DRAWING |
| | |
| | 18. MP-4: NOTE 3: PER FBC PL 607.1, PROVIDE HOT WATER |
| | AND COLD WATER |
| | |
| | 19. MP-4: NOTE 11: PER FBC PL 712.2, A CHECK VALVE AND |
| | A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE |
| | LINE FROM THE SUMP AND SHALL BE ACCESSIBLE. |
| | |
| | 20. MP-4: NOTE 10: PROVIDE DETAIL(S) FOR UTILITIES |
| | CONNECTION(S) OR DISPOSAL POINTS |
| | |
| | 21. MP-4: PROVIDE NOTE FOR SUMP DISCHARGE CONNECTION TO |
| | BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO |
| | THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER, |
| | BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL |
| | BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE |
| | MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS |
| | THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK, |
| | WASTE STACK OR FIXTURE DRAIN.? |
| | |
| | 22. MP-5: NOTE 4; PER FBC PL 607.1, PROVIDE HOT WATER |
| | AND COLD WATER |
| | |
| | 23. MP-6: ADD TO NOTE 8, ?VENT TERMINALS EXTENDING |
| | THROUGH THE WALL SHALL COMPLY WITH FBC PL 903.6? |
| | |
| | 24. MP-8: STORM DRAIN PIPING AT FD; REPLACE P-TRAP WITH |
| | QUARTER BEND SWEEP. SEE FBC PL 1002.3, 1101.6 AND |
| | 1103.1 |
| | |
| | 25. MP-8: PROVIDE AN INDIVIDUAL VENT FOR P-4 SERVICE |
| | SINK. SHOW COMPLIANCE WITH FBC PL 909.1 AND 1002.3(5) |
| | |
| | 26. MP-8: P-1 WATER CLOSET IS A WALL HUNG FIXTURE. PER |
| | WPB FBC 107.2.1, SHOW IN THE SANITARY RISER AS ABOVE |
| | FLOOR WALL CONNECTION. |
| | |
| | 27. MP-8: STORM RISER; PER WPB FBC 107.2.1, INCLUDE |
| | STORM DISCHARGE PIPING FROM SUMP. |
| | |
| | 28. MP-8: PROVIDE NOTE FOR PUMP DISCHARGE CONNECTION TO |
| | BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO |
| | THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER, |
| | BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL |
| | BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE |
| | MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS |
| | THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK, |
| | WASTE STACK OR FIXTURE DRAIN.? |
| | |
| | 29. MP-8: PROVIDE HOT WATER ROUTING OR TANKLESS WATER |
| | HEATERS FOR P-3, P-4 IN WATER RISER BELOW P-2. IF |
| | PROVIDING ROUTING, SPECIFY TANKLESS HEATER THAT WILL |
| | ACCOMMODATE P-2, P-3 AND P-4. |
| | |
| | 30. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 31. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC |
| | FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, FITTINGS AND |
| | JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND 11. |
| | ?A) ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | ?B) DISCHARGE PIPING FROM SUMP PUMPS SHALL BE PRESSURE |
| | RATED IN ACCORDANCE WITH FBC PL SECTIONS 712.3.3.1 AND |
| | 712.3.3.2, PROVIDE NOTE ON PLANS STATING THE SAME. |
| | |
| | 32.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT |
| | WATER PIPING AND CONDENSATE PIPING INSULATION |
| | |
| | 33. MORE INFORMATION IS REQUIRED REGARDING THE STORM |
| | DRAIN. WHAT IS THE PURPOSE? IS THIS IN AN OPEN AREA |
| | SUBJECT TO RAINFALL? |
| | ?A) PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE |
| | CALCULATIONS FOR SIZING THE GRAVITY DRAIN COMPLYING |
| | WITH FBC PL TABLES 1106.2 AND 1106.3. |
| | ?B) NOTE THE REQUIRED SLOPE FOR THE HORIZONTAL PIPING. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | 21100652 401 CLEMATIS ST |
| | |
| | |
| | |
| 2021-11-12 07:09:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21100652 401 CLEMATIS ST |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: |
| | 1.GENERAL NOTE: DEFERRED SUBMITTALS FBC 107.3.4.1 |
| | REGARDING THE SUMP PUMP, POINT OF USE WATER HEATERS, |
| | ETC., DEFERRED SUBMITTALS IN THE FORM OF MANUFACTURERS |
| | SPECIFICATIONS/INSTALLATION INSTRUCTIONS MAY BE |
| | SUBMITTED IN ACCORDANCE WITH WPB FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL |
| | BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND |
| | ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | BY PROVIDING THE NOTE ABOVE ON THE CONSTRUCTION |
| | DOCUMENTS TO BE REVIEWED AND LISTING THE ITEMS TO BE |
| | DEFERRED, YOU MAY PROCEED IN THIS MANNER. |
| | |
| | 2.A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | THE RESTROOM DOES NOT APPEAR TO COMPLY WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6. PER WPB FBC 107.2.1, CLARIFY. |
| | PLEASE REVIEW FBC ACC 203.9, 213.1. PROVIDE ELEVATIONS |
| | AND PLAN VIEW SHOWING COMPLIANCE WITH FBC ACC AS |
| | FOLLOWS AND IS APPLICABLE. |
| | ?A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | ?B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | ?C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | ?D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | ?E) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET PER FBC ACC 604.6 |
| | ?F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | ?G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| | FBC ACC 604.4. |
| | ?H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN |
| | A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT |
| | THE CENTER) OF THE GRIPPING SURFACE, |
| | ?I) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO |
| | THE ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED |
| | IN THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION |
| | FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER |
| | CLOSET. |
| | ?J)LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | ?K) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5 |
| | PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 |
| | PER FBC ACC 212.3. DOES NOT APPLY TO A SERVICE SINK. |
| | ?L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. |
| | ?M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. |
| | ?N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | ?O) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 |
| | OR 304.3.2. |
| | |
| | 3.PER WPB FBC 107.2.1, PROVIDE OCCUPANCY TYPE AND |
| | OCCUPANCY LOAD FOR STRUCTURE. PROVIDE FIXTURE SCHEDULE |
| | LISTING REQUIRED PLUMBING FIXTURES AND QUANTITIES |
| | REQUIRED BY FBC PL TABLE 403.1 TO ACCOMMODATE THE |
| | STATED OCCUPANCY AND OCCUPANCY LOAD. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE AN OVERALL FLOOR PLAN |
| | FOR EACH LEVEL SHOWING RESPECTIVE LOCATIONS OF PIER 6 |
| | AND PIER 7 AS WELL AS COMPREHENSIVE ELEVATION VIEW(S) |
| | IDENTIFYING THE LEVELS. |
| | |
| | 5. MP-1: PER WPB FBC 107.2.1, SPECIFY A CARRIER SYSTEM |
| | FOR P-1 WATER CLOSET; PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL FOR CARRIER SYSTEM |
| | FOR P-1 WATER CLOSET OR LIST AS A DEFERRED SUBMITTAL IN |
| | ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL FOR CARRIER FOR P-2 |
| | LAVATORY OR LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE |
| | WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 7. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; PER WPB FBC |
| | 107.2.1, PROVIDE SUMP PUMP AND BASIN DETAIL SHOWING |
| | PIPING AND VALVE ARRANGEMENT SHOWING COMPLIANCE WITH |
| | FBC PL SECTION 712. PER FBC PL 712.2, A CHECK VALVE AND |
| | A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE |
| | LINE FROM THE SUMP AND SHALL BE ACCESSIBLE. |
| | |
| | 8. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR SUMP PUMP OR LIST AS A DEFERRED SUBMITTAL IN |
| | ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 9. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; A VACUUM |
| | BREAKER IS REQUIRED ON THE FAUCET HOSE THREADS PER FBC |
| | PL 608.1 AND 608.2. PER WPB FBC 107.2.1, SPECIFY AND |
| | ADD TO P-4 DESCRIPTION. |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE TANKLESS WATER HEATER |
| | INSTALLATION DETAIL SHOWING PIPING AND VALVE |
| | ARRANGEMENT. |
| | |
| | 11. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE WATER HEATERS OR LIST AS A DEFERRED |
| | SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT |
| | #1. |
| | |
| | 12. MP-1: FIXTURE SCHEDULE P-2 LAVATORY; FBC PL 419.5 |
| | REQUIRES COLD OR TEMPERED WATER SHALL BE DELIVERED FROM |
| | LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC |
| | TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. |
| | ?A) PER WPB FBC 107.2.1, PLEASE CLARIFY IF THERE IS TO |
| | BE PUBLIC ACCESS TO THE RESTROOM. COMPLIANT TEMPERED |
| | WATER DEVICES MAY BE PROVIDED IN ANY CASE BUT SHALL BE |
| | PROVIDED IF PUBLIC. |
| | ?B) PER WPB FBC 107.2.1, A SPECIFICATION WOULD BE |
| | REQUIRED. |
| | |
| | 13. P-3 SINK AND P-4 SINK IN RISER BELOW P-2 LAVATORY, |
| | PER FBC PL 607.1, PROVIDE HOT WATER. |
| | |
| | 14. PROVIDE DETAIL FOR HB-1 WALL BOX AND SHUTOFF VALVE. |
| | WILL WALL BOX BE RECESSED INTO STRUCTURE? |
| | |
| | 15. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE WALL BOX OR LIST AS A DEFERRED SUBMITTAL |
| | IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1. |
| | |
| | 16. MP-2: TAG NOTE 1: SUMP PIT AND PUMP BY OTHERS; PER |
| | WPB FBC 107.2.1, PROVIDE DETAIL FOR SUMP PIT AND PUMP |
| | BY OTHERS SHOWING DIMENSIONS, PIPING AND VALVE |
| | ARRANGEMENT. COMPLY WITH FBC PL SECTION 712. PER FBC PL |
| | 712.2, A CHECK VALVE AND A FULL OPEN VALVE SHALL BE |
| | LOCATED IN THE DISCHARGE LINE FROM THE SUMP AND SHALL |
| | BE ACCESSIBLE. ADDITIONALLY, INDICATE THE PUMP |
| | DISCHARGE GPM SHOWING IT IS CAPABLE OF DISCHARGING THE |
| | COMBINED STORM WATER AND A/C CONDENSATE ENTERING THE |
| | PIT. |
| | |
| | 17. MP-2: TAG NOTE 4: REFERS TO B1-424 FOR ADDITIONAL |
| | INFORMATION. PER WPB FBC 107.2.1, PROVIDE REFERENCED |
| | DRAWING |
| | |
| | 18. MP-4: NOTE 3: PER FBC PL 607.1, PROVIDE HOT WATER |
| | AND COLD WATER |
| | |
| | 19. MP-4: NOTE 11: PER FBC PL 712.2, A CHECK VALVE AND |
| | A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE |
| | LINE FROM THE SUMP AND SHALL BE ACCESSIBLE. |
| | |
| | 20. MP-4: NOTE 10: PROVIDE DETAIL(S) FOR UTILITIES |
| | CONNECTION(S) OR DISPOSAL POINTS |
| | |
| | 21. MP-4: PROVIDE NOTE FOR SUMP DISCHARGE CONNECTION TO |
| | BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO |
| | THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER, |
| | BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL |
| | BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE |
| | MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS |
| | THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK, |
| | WASTE STACK OR FIXTURE DRAIN.? |
| | |
| | 22. MP-5: NOTE 4; PER FBC PL 607.1, PROVIDE HOT WATER |
| | AND COLD WATER |
| | |
| | 23. MP-6: ADD TO NOTE 8, ?VENT TERMINALS EXTENDING |
| | THROUGH THE WALL SHALL COMPLY WITH FBC PL 903.6? |
| | |
| | 24. MP-8: STORM DRAIN PIPING AT FD; REPLACE P-TRAP WITH |
| | QUARTER BEND SWEEP. SEE FBC PL 1002.3, 1101.6 AND |
| | 1103.1 |
| | |
| | 25. MP-8: PROVIDE AN INDIVIDUAL VENT FOR P-4 SERVICE |
| | SINK. SHOW COMPLIANCE WITH FBC PL 909.1 AND 1002.3(5) |
| | |
| | 26. MP-8: P-1 WATER CLOSET IS A WALL HUNG FIXTURE. PER |
| | WPB FBC 107.2.1, SHOW IN THE SANITARY RISER AS ABOVE |
| | FLOOR WALL CONNECTION. |
| | |
| | 27. MP-8: STORM RISER; PER WPB FBC 107.2.1, INCLUDE |
| | STORM DISCHARGE PIPING FROM SUMP. |
| | |
| | 28. MP-8: PROVIDE NOTE FOR PUMP DISCHARGE CONNECTION TO |
| | BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO |
| | THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER, |
| | BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL |
| | BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE |
| | MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS |
| | THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK, |
| | WASTE STACK OR FIXTURE DRAIN.? |
| | |
| | 29. MP-8: PROVIDE HOT WATER ROUTING OR TANKLESS WATER |
| | HEATERS FOR P-3, P-4 IN WATER RISER BELOW P-2. IF |
| | PROVIDING ROUTING, SPECIFY TANKLESS HEATER THAT WILL |
| | ACCOMMODATE P-2, P-3 AND P-4. |
| | |
| | 30. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 31. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC |
| | FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, FITTINGS AND |
| | JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND 11. |
| | ?A) ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | ?B) DISCHARGE PIPING FROM SUMP PUMPS SHALL BE PRESSURE |
| | RATED IN ACCORDANCE WITH FBC PL SECTIONS 712.3.3.1 AND |
| | 712.3.3.2, PROVIDE NOTE ON PLANS STATING THE SAME. |
| | |
| | 32.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT |
| | WATER PIPING AND CONDENSATE PIPING INSULATION |
| | |
| | 33. MORE INFORMATION IS REQUIRED REGARDING THE STORM |
| | DRAIN. WHAT IS THE PURPOSE? IS THIS IN AN OPEN AREA |
| | SUBJECT TO RAINFALL? |
| | ?A) PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE |
| | CALCULATIONS FOR SIZING THE GRAVITY DRAIN COMPLYING |
| | WITH FBC PL TABLES 1106.2 AND 1106.3. |
| | ?B) NOTE THE REQUIRED SLOPE FOR THE HORIZONTAL PIPING. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | 21100652 401 CLEMATIS ST |
| | |
| | |
| | |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| | AVOID VOIDING OF THE PERMIT. |
| | |
| | NOTE: PER WPB FBC 105.1, A PLUMBING SUB-PERMIT IS |
| | REQUIRED. |
| | |
| | 1.NEW COMMENT: FALLS UNDER THE RULES OF THE FAIR |
| | HOUSING ACT. IN ACCORDANCE WITH WPB FBC 107.2.1, |
| | INDICATE ON THE FLOOR PLAN, COMPLIANCE WITH THE FAIR |
| | HOUSING ACT, INDICATING TYPE OF BATHROOM(S), (TYPE A, |
| | TYPE B), IN ACCORDANCE WITH GUIDELINES UNDER |
| | REQUIREMENT 7, INCLUDING CLEAR FLOOR SPACE AND |
| | MANEUVERING. ALTERNATIVELY YOU MAY SUBMIT A REQUEST FOR |
| | WAIVER IN THE FORM OF A LETTER SHOWN BELOW. THIS SHOULD |
| | BE SIGNED BY BOTH PARTIES (DESIGNER AND OWNER), BUT |
| | ONLY THE OWNER?S SIGNATURE NEEDS TO BE NOTARIZED. |
| | |
| | PROJECT ADDRESS: ______________________________________ |
| | _____________________ |
| | PERMIT NUMBER: ________________________ |
| | THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| | PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS |
| | OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER |
| | AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF |
| | SALE IF SO REQUESTED BY THE BUYER. |
| | |
| | SIGNATURE OF DESIGNER: ______________________________ |
| | PRINTED NAME OF DESIGNER: ___________________________ |
| | |
| | SIGNATURE OF OWNER: ________________________________ |
| | PRINTED NAME OF OWNER: _____________________________ |
| | NOTARY FOR OWNER?S SIGNATURE: |
| | STATE OF FLORIDA, COUNTY OF PALM BEACH |
| | THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| | THIS _____ DAY OF ________, 20__ BY |
| | ___________________________ WHO IS PERSONALLY KNOWN TO |
| | ME OR WHO HAS PRODUCED: ___________________________ AS |
| | IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| | NOTARY SIGNATURE ___________________________________ |
| | NOTARY PRINTED NAME ________________________________ |
| | |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.2.1, A PAPER PLAN |
| | WITH WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING |
| | DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A |
| | PERMIT. |
| | |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.2, A PAPER |
| | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | |
| | PHONE 561-805-6715 |
| | PLUMBING COMMENTS: APPROVED |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | PLUMBING COMMENTS: APPROVED WITH PROVISO |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PER WPB FBC 107.1,ALL PLANS TO BE SIGNED AND SEALED BY |
| | THE DESIGNER IN ACCORDANCE WITH FAC AND FS. DESIGNER TO |
| | PROVIDE DIGITAL SIGNATURE IN ACCORDANC WITH FAC AND FS |
| | OR SHALL PROVIDE SIGNED AND SEALED PAPER DOCUMENT PRIOR |
| | TO PERMIT ISSUANCE.CALL 561-805-6724 FOR ADDITIONAL |
| | INFORMATION |
| | SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| | PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER |
| | 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL, |
| | 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR |
| | THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL |
| | ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER |
| | THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| | DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE |
| | CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE |
| | LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND |
| | LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY |
| | ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED AS A |
| | BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT |
| | ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | 1.PLEASE REFER TO BUILDING PLANS EXAMINER?S COMMENTS: |
| | 1) THE BUILDING CONTRACTOR HAS NOT TAKEN RESPONSIBILITY |
| | FOR THE DESIGN/ CREATION OF THE FLOOR PLAN AND KITCHEN |
| | ELEVATION PLANS. THE CONTRACTOR (QUALIFIER) THAT |
| | CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | |
| | A COMPREHENSIVE |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | |
| | AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING |
| | PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR |
| | THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| | NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| | LICENSED IN THAT TRADE. |
| | |
| | CONTRACTOR AS DESIGNER) THE FLOOR PLAN WAS NOT DESIGNED |
| | BY EITHER AN ENGINEER OR ARCHITECT. CERTIFICATION BY |
| | CONTRACTOR. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| | DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS DRAWN. 107.3.4.3 CERTIFICATION BY |
| | CONTRACTOR. |
| | |