| 2022-03-16 13:08:27 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21100650 |
| | 3/16/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #8 FROM THE |
| | 1ST AND 2ND REVIEW IS LISTED BELOW WITH ADDITIONAL |
| | NOTES IN CAP LETTERS. |
| | |
| | 8) FAILED. A2.4: PROVIDE ROOF DRAINAGE CALCULATIONS AND |
| | SHOW THE PRIMARY AND SECONDARY SCUPPER LOCATIONS- |
| | SECTIONS 1105 & 1106 FBC P. PLEASE PROVIDE SCUPPER |
| | CONSTRUCTION DETAILS IN ACCORDANCE WITH SECTIONS 1503.2 |
| | AND 1503.2.4.1 FBC B. SECONDARY (OVERFLOW) SCUPPER |
| | LOCATIONS AND OPENING DIMENSIONS NOT SHOWN- SEE SEC. |
| | 1108.2, 1108.3 FBC P, AND SEC. 1503.4.2 FBC B. |
| | |
| | A) REFER TO SEC. 1106.4 AND INCLUDE THE DRAINAGE |
| | CALCULATIONS FOR THE PARAPET WALLS. |
| | |
| | B) THE 5X7-INCH SCUPPER OPENING IS NOT REFLECTED IN THE |
| | DRAWINGS WHICH SHOWS A MAX 4-INCH HEIGHT OPENING, AND |
| | NO WIDTH OPENING PROVIDED- SEC. 1106.5 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |