2022-03-16 13:08:273RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21100650
 3/16/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #8 FROM THE
 1ST AND 2ND REVIEW IS LISTED BELOW WITH ADDITIONAL
 NOTES IN CAP LETTERS.
  
 8) FAILED. A2.4: PROVIDE ROOF DRAINAGE CALCULATIONS AND
 SHOW THE PRIMARY AND SECONDARY SCUPPER LOCATIONS-
 SECTIONS 1105 & 1106 FBC P. PLEASE PROVIDE SCUPPER
 CONSTRUCTION DETAILS IN ACCORDANCE WITH SECTIONS 1503.2
 AND 1503.2.4.1 FBC B. SECONDARY (OVERFLOW) SCUPPER
 LOCATIONS AND OPENING DIMENSIONS NOT SHOWN- SEE SEC.
 1108.2, 1108.3 FBC P, AND SEC. 1503.4.2 FBC B.
  
 A) REFER TO SEC. 1106.4 AND INCLUDE THE DRAINAGE
 CALCULATIONS FOR THE PARAPET WALLS.
  
 B) THE 5X7-INCH SCUPPER OPENING IS NOT REFLECTED IN THE
 DRAWINGS WHICH SHOWS A MAX 4-INCH HEIGHT OPENING, AND
 NO WIDTH OPENING PROVIDED- SEC. 1106.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  