| 2022-02-02 10:34:19 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21100650 |
| | 2/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #3 & 8 |
| | FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES IN CAP LETTERS. |
| | |
| | 3) FAILED. P401, P601: INDICATE HOW TEMPERED WATER WILL |
| | BE DELIVERED FROM THE LAVATORIES- 419.5 FBC P. TEMPERED |
| | WATER IS WATER WITH A TEMPERATURE BETWEEN 85?F AND |
| | 110?F, NOT 110 F- SEC. 202 FBC P. PROVIDE A MIXING |
| | VALVE FOR THE HW AND CW SUPPLY LINES TO THE LAVATORY- |
| | SEC. 607.1.2 FBC P. |
| | |
| | 8) FAILED. A2.4: PROVIDE ROOF DRAINAGE CALCULATIONS AND |
| | SHOW THE PRIMARY AND SECONDARY SCUPPER LOCATIONS- |
| | SECTIONS 1105 & 1106 FBC P. PLEASE PROVIDE SCUPPER |
| | CONSTRUCTION DETAILS IN ACCORDANCE WITH SECTIONS 1503.2 |
| | AND 1503.2.4.1 FBC B. SECONDARY SCUPPER LOCATIONS AND |
| | OPENING DIMENSIONS NOT SHOWN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |