2022-02-02 10:34:192ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21100650
 2/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #3 & 8
 FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES IN CAP LETTERS.
  
 3) FAILED. P401, P601: INDICATE HOW TEMPERED WATER WILL
 BE DELIVERED FROM THE LAVATORIES- 419.5 FBC P. TEMPERED
 WATER IS WATER WITH A TEMPERATURE BETWEEN 85?F AND
 110?F, NOT 110 F- SEC. 202 FBC P. PROVIDE A MIXING
 VALVE FOR THE HW AND CW SUPPLY LINES TO THE LAVATORY-
 SEC. 607.1.2 FBC P.
  
 8) FAILED. A2.4: PROVIDE ROOF DRAINAGE CALCULATIONS AND
 SHOW THE PRIMARY AND SECONDARY SCUPPER LOCATIONS-
 SECTIONS 1105 & 1106 FBC P. PLEASE PROVIDE SCUPPER
 CONSTRUCTION DETAILS IN ACCORDANCE WITH SECTIONS 1503.2
 AND 1503.2.4.1 FBC B. SECONDARY SCUPPER LOCATIONS AND
 OPENING DIMENSIONS NOT SHOWN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  