| 2021-12-03 15:35:02 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21100650 |
| | 12/03/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A2.1 & A2.3 FBC ACCESSIBILITY CORRECTIONS: |
| | A) SHOW THE 56 X 60 INCHES MINIMUM CLEAR FLOOR SPACE |
| | DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET- SECTION |
| | 604.3. |
| | B) SHOW THE 30 X 48 INCHES MINIMUM CLEAR FLOOR SPACE |
| | DIAGRAM AND DIMENSIONS FOR THE LAVATORY- 606.2. |
| | C) SHOW THE TURNING SPACE DIAMETER- 304.3. |
| | D) SHOW THE 40-INCH HEIGHT OF THE MIRROR FROM THE |
| | FINISHED FLOORS TO THE REFLECTIVE SURFACE- 603.3 |
| | E) SHOW THE LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THAT THE HEIGHT |
| | MEASUREMENT SHALL BE BE TO THE TOPES OF THE BAR |
| | GRIPPING SURFACES. |
| | F) SHOW THE LOCATION OF THE WATER CLOSET FLUSH CONTROL |
| | ON THE OPEN SIDE OF THE FIXTURE- 604.6. |
| | G) THE CENTERLINES OF THE TOILET PAPER DISPENSER SHALL |
| | BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM MEASURED FROM |
| | THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| | 604.7. |
| | H) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2 AND FIGURES 306.2 & 306.3 |
| | I) SHOW A MINIMUM 30X48-INCH CLEAR FLOOR SPACE APPROACH |
| | AT THE DRINKING FOUNTAIN- 602.2. |
| | J) SHOW THE SPOUT HEIGHT OF THE DRINKING FOUNTAIN- |
| | 602.4. |
| | H) IT APPEARS A PARALLEL APPROACH WILL BE USED FOR THE |
| | KITCHENETTE SINK. PLEASE SHOW A MINIMUM 30X48 INCH |
| | CLEAR FLOOR SPACE AT THE SINK- 606.2. |
| | |
| | 2) A2.3: PLEASE CORRECT THE NOTE SPECIFYING PAINTED |
| | GYPSUM BOARD FOR THE WALLS SURROUNDING THE WATER |
| | CLOSET. IN ACCORDANCE WITH SECTION 310.3 FBC P AND |
| | 1210.2.2 FBC B- WALLS AND PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. THE WPB BUILDING DEPARTMENT DOES NOT ACCEPT |
| | PAINTED GYPSUM BOARD AS A COMPLIANT MATERIAL. PLEASE |
| | PROVIDE TILE, FRP, OR OTHER SMOOTH, HARD, NON-ABSORBENT |
| | MATERIAL FOR THE WALLS AROUND THE WATER CLOSET AND MOP |
| | SINK. |
| | |
| | 3) P401, P601: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- 419.5 FBC P. |
| | |
| | 4) P401, P601, P701: THE PLAN SHOWS NON-COMPLIANCE WITH |
| | SECTION & TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS |
| | A MAXIMUM ALLOWABLE LENGTH OF 2FT. FROM THE NEAREST HOT |
| | WATER SOURCE TO THE FIXTURE SUPPLY PIPE AT THE |
| | LAVATORIES. PLEASE PROVIDE EITHER POINT OF USE WATER |
| | HEATERS AT THE LAVATORIES OR A HOT WATER RECIRCULATION |
| | PUMP. |
| | |
| | 5) P401, P601, P801: PLEASE PROVIDE SYMBOLS TO THE |
| | LOCATIONS OF WATER HAMMER ARRESTORS AND BACKFLOW |
| | PREVENTERS- SECTIONS 604.9 & 608.3 FBC P. |
| | |
| | 6) P801: PLEASE PROVIDE THE LISTING STANDARDS FOR THE |
| | BACKFLOW PREVENTERS SHOWN IN THE SCHEDULE- TABLE 608.3 |
| | FBC P. |
| | |
| | 7) P701: SHOW THE LOCATION OF THE WATER HEATER |
| | EXPANSION TANK IN THE DETAIL- SECTION 607.3 FBC P. |
| | |
| | 8) A2.4: PROVIDE ROOF DRAINAGE CALCULATIONS AND SHOW |
| | THE PRIMARY AND SECONDARY SCUPPER LOCATIONS- SECTIONS |
| | 1105 & 1106 FBC P. PLEASE PROVIDE SCUPPER CONSTRUCTION |
| | DETAILS IN ACCORDANCE WITH SECTIONS 1503.2 AND |
| | 1503.2.4.1 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |