| Plan Review Notes For Permit 21100650 |
| Permit Number |
21100650 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-23 09:27:17 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21100650 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M801: PLEASE USE THE 2020 FBC M AND ASHRAE | | | 62.1-2016 EDITION REFERENCED IN THE 2020 FBC M. | | | | | | 2) THE CONFERENCE ROOM OUTDOOR AIR IS LOW. PER FBC M | | | 403.3.1.1 AND TABLE 403.3.1.1 THE OCCUPANT LOAD FOR | | | THIS CONFERENCE ROOM IS 14 WHICH WOULD MAKE THE | | | CALCULATION COME OUT TO BE 87 CFM OF OUTDOOR AIR | | | REQUIRED FOR THIS CONFERENCE ROOM. PLEASE MAKE THE | | | CORRECTIONS. | | | | | | 3) THE TOTAL OUTDOOR AIR FOR THE AHU WOULD BE 152 | | | CFM?S. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND | | | TERMINATION LOCATION. FBC M 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|