Plan Review Notes
Plan Review Notes For Permit 21100650
Permit Number 21100650
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-11-22 10:28:28LIFE SAFETY PLAN SHEET A2.1 NOTE 1 STATES THE FIRE
 ALARM PLAN WITH DEVICE LOCATIONS ARE LOCATED ON THE
 ELECTRICAL PLANS. INSUFFICIENT INFORMATION FOR REVIEW
 IS INCLUDED ON THE ELECTRICAL SHEETS FOR FIRE ALARM
 INSTALLATION (FACP, DEVICE PLACEMENT, ETC.). EITHER
 INCLUDE A NOTE THAT THE FIRE ALARM WILL BE SUBMITTED
 UNDER A SEPARATE PERMIT, OR HAVE COMPLETE FIRE ALARM
 DETAILS FOR FIRE ALARM REVIEW. NFPA 72 10.4.1