| Plan Review Notes For Permit 21100650 |
| Permit Number |
21100650 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-22 10:28:28 | LIFE SAFETY PLAN SHEET A2.1 NOTE 1 STATES THE FIRE | | | ALARM PLAN WITH DEVICE LOCATIONS ARE LOCATED ON THE | | | ELECTRICAL PLANS. INSUFFICIENT INFORMATION FOR REVIEW | | | IS INCLUDED ON THE ELECTRICAL SHEETS FOR FIRE ALARM | | | INSTALLATION (FACP, DEVICE PLACEMENT, ETC.). EITHER | | | INCLUDE A NOTE THAT THE FIRE ALARM WILL BE SUBMITTED | | | UNDER A SEPARATE PERMIT, OR HAVE COMPLETE FIRE ALARM | | | DETAILS FOR FIRE ALARM REVIEW. NFPA 72 10.4.1 |
|