| 2021-11-16 12:53:24 | THE ENERGY CALCULATION SHOW THE SYSTEM SERVES THE WHOLE | | | HOUSE, NOT OTHER AND IDENTIFIES THE CORRECT AREA. | | | PLEASE IDENTIFY THE CORRECT AREA SERVED BY THIS UNIT. | | | THE ENERGY CALCULATIONS SHOW THE LOCATION IS BROWARD | | | COUNTY FL. PLEASE CORRECT THIS TO WEST PALM BEACH. | | | THE ENERGY CALCULATIONS DO NOT MENTION THE GARAGE DOOR, | | | PLEASE SHOW THIS IN THE CALCULATIONS. | | | THE ENERGY CALCULATIONS INDICATE THE CONDITIONED AREA | | | IS 735 SQ FT AND 1 BEDROOM. IS THIS GARAGE BEING | | | CONVERTED TO A BEDROOM? | | | THE ENERGY CALCULATION INDICATES THE DESIGN IS FOR | | | 70DEG HEATING AND 75 DEG FOR COOLING BUT EQUIPMENT TYPE | | | IS FOR COOLING-ONLY AIR CONDITIONER. | | | THE DUCT DESIGN IS FOR 688 SQ FT BUT THE CONDITIONED | | | FLOOR AREA USED IN LOADS IS 735 SQ. FT. PLEASE BE | | | CONSISTENT. | | | PLEASE SHOW THE SEER RATING IN THE ENERGY CALCULATIONS. | | | THE ENERGY CALCULATIONS, UNDER THE RESNET, IT LISTS | | | THAT THE FURNACE HEATING EFFICIENCY IS 80 AFUE. WHERE | | | IS THIS FURNACE LOCATED? | | | PLEASE PROVIDE CODE COMPLIANT DOCUMENTS. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|