Plan Review Notes
Plan Review Notes For Permit 21100623
Permit Number 21100623
Review Stop M
Sequence Number 2
Notes
Date Text
2021-11-16 12:53:24THE ENERGY CALCULATION SHOW THE SYSTEM SERVES THE WHOLE
 HOUSE, NOT OTHER AND IDENTIFIES THE CORRECT AREA.
 PLEASE IDENTIFY THE CORRECT AREA SERVED BY THIS UNIT.
 THE ENERGY CALCULATIONS SHOW THE LOCATION IS BROWARD
 COUNTY FL. PLEASE CORRECT THIS TO WEST PALM BEACH.
 THE ENERGY CALCULATIONS DO NOT MENTION THE GARAGE DOOR,
 PLEASE SHOW THIS IN THE CALCULATIONS.
 THE ENERGY CALCULATIONS INDICATE THE CONDITIONED AREA
 IS 735 SQ FT AND 1 BEDROOM. IS THIS GARAGE BEING
 CONVERTED TO A BEDROOM?
 THE ENERGY CALCULATION INDICATES THE DESIGN IS FOR
 70DEG HEATING AND 75 DEG FOR COOLING BUT EQUIPMENT TYPE
 IS FOR COOLING-ONLY AIR CONDITIONER.
 THE DUCT DESIGN IS FOR 688 SQ FT BUT THE CONDITIONED
 FLOOR AREA USED IN LOADS IS 735 SQ. FT. PLEASE BE
 CONSISTENT.
 PLEASE SHOW THE SEER RATING IN THE ENERGY CALCULATIONS.
 THE ENERGY CALCULATIONS, UNDER THE RESNET, IT LISTS
 THAT THE FURNACE HEATING EFFICIENCY IS 80 AFUE. WHERE
 IS THIS FURNACE LOCATED?
 PLEASE PROVIDE CODE COMPLIANT DOCUMENTS. FBC 107.2.1
  