Plan Review Notes
Plan Review Notes For Permit 21100616
Permit Number 21100616
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-14 12:00:0912/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET AG2.01;
  
 A.UNGER GENERAL NOTES NUMBER 3 REFERS TO THE ADA
 STANDARD AND THE CODE REFERENCE THAT SHOULD BE USED IS
 THE 2020 FLORIDA BUILDING CODE ACCECIBILTY 7 TH EDITION
 PER THE WPB AMENDMENTS TO FBC 102.3 APPLICATION OF
 REFERENCES. WOULD PLEASE4 REFER TO THE FOLLOWING IF
 PREFERRED HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA. ITEM
 FOUR IS NOT REQUIRED.
  
 B. GRAB BARS SHALL BE INSTALLED HORIZONTALLY PER THE
 2020 FBC ACC SEC. 609.4.
  
 C. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY
 CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE
 2020 FBC ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 D. THE TOILET SEATS NEED TO BE 17 INCHES TO 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020
 FBC ACC SEC. 604.4 SEATS.
  
 E. A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC. 410.3.
  
 F. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 2. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE
 COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. ON SHEET LS1.01;
  
 A. IT HAS THE CODE REFERENCE SAYING 2017 FOR PLUMBING.
 WOULD YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNDER PLUMB=ING FIXTURE CALCULATION, IT REQUIRES A
 SERVICE SINK, AND I DON'T SEE ANY LOCATION NEARBY.
 WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET P0.01;
  
 A. UNDER PLUMBING SPECIFICATIONS 2.1, THE 2018
 INTERNATIONAL PLUMBING CODE IS REFERENCED, AND WE GO BY
 THE 2020 FLORIDA PLUMBING CODE PER THE WPB AMENDMENTS
 TO FBC 102.3 APPLICATION OF REFERENCES.
  
 B. THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE
 SEC. C404.6.1. B. HOT WATER LINES LOOPED FOR THE
 RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE AND
 THE OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE
 MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 C. ON ISOMETRIC, THE DRINKING FOUNTAIN DOES NOT SHOW A
 HAMMER ARRESTOR PER THE 2020 FBC SEC. P604.9.
  
 D. FIXTURES UNDER THE COFFEE MAKER/ICE MAKER REQUIRE AN
 INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024
 NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  