| 2021-12-14 12:00:09 | 12/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. ON SHEET AG2.01; |
| | |
| | A.UNGER GENERAL NOTES NUMBER 3 REFERS TO THE ADA |
| | STANDARD AND THE CODE REFERENCE THAT SHOULD BE USED IS |
| | THE 2020 FLORIDA BUILDING CODE ACCECIBILTY 7 TH EDITION |
| | PER THE WPB AMENDMENTS TO FBC 102.3 APPLICATION OF |
| | REFERENCES. WOULD PLEASE4 REFER TO THE FOLLOWING IF |
| | PREFERRED HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA. ITEM |
| | FOUR IS NOT REQUIRED. |
| | |
| | B. GRAB BARS SHALL BE INSTALLED HORIZONTALLY PER THE |
| | 2020 FBC ACC SEC. 609.4. |
| | |
| | C. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL, |
| | WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16 |
| | INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY |
| | CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE |
| | 2020 FBC ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | D. THE TOILET SEATS NEED TO BE 17 INCHES TO 19 INCHES |
| | MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020 |
| | FBC ACC SEC. 604.4 SEATS. |
| | |
| | E. A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC. 410.3. |
| | |
| | F. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| | 2020 FBC P 425.3 WATER CLOSET SEATS. |
| | |
| | 2. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING |
| | THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE |
| | COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 3. ON SHEET LS1.01; |
| | |
| | A. IT HAS THE CODE REFERENCE SAYING 2017 FOR PLUMBING. |
| | WOULD YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. UNDER PLUMB=ING FIXTURE CALCULATION, IT REQUIRES A |
| | SERVICE SINK, AND I DON'T SEE ANY LOCATION NEARBY. |
| | WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. ON SHEET P0.01; |
| | |
| | A. UNDER PLUMBING SPECIFICATIONS 2.1, THE 2018 |
| | INTERNATIONAL PLUMBING CODE IS REFERENCED, AND WE GO BY |
| | THE 2020 FLORIDA PLUMBING CODE PER THE WPB AMENDMENTS |
| | TO FBC 102.3 APPLICATION OF REFERENCES. |
| | |
| | B. THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE |
| | SEC. C404.6.1. B. HOT WATER LINES LOOPED FOR THE |
| | RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP. |
| | THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE AND |
| | THE OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE |
| | MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE |
| | ACCORDANTLY. |
| | |
| | C. ON ISOMETRIC, THE DRINKING FOUNTAIN DOES NOT SHOW A |
| | HAMMER ARRESTOR PER THE 2020 FBC SEC. P604.9. |
| | |
| | D. FIXTURES UNDER THE COFFEE MAKER/ICE MAKER REQUIRE AN |
| | INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024 |
| | NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |