2021-12-06 08:19:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100616
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION FOR THE
 PRE-OP, PROCEDURE AND POST-OP ROOMS. FBC M 407
  
 2) THE EXHAUST TRUNK HAS A BRANCH EXTENSION OUTSIDE OF
 THE EX-TOILET TO THE RIGHT OF THE LAB. IS THIS
 EXTENSION FOR THE STORAGE AREA OUTSIDE OF THE LAB?
  
 3) THE EXISTING HP-2 APPEARS TO HAVE A DAMPER FOR A
 RETURN IN EXAM 3 BUT THERE IS NO DUCT TIED TO THE
 RETURN GRILLE.
  
 4) THE EXISTING HP-5 HAS A DAMPER FOR A RETURN AIR DUCT
 AT THE END OF THE 8 X 12 DUCT BUT IT DOESN?T CONNECT TO
 A RETURN AIR GRILLE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  