| Plan Review Notes For Permit 21100616 |
| Permit Number |
21100616 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-06 08:19:58 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21100616 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION FOR THE | | | PRE-OP, PROCEDURE AND POST-OP ROOMS. FBC M 407 | | | | | | 2) THE EXHAUST TRUNK HAS A BRANCH EXTENSION OUTSIDE OF | | | THE EX-TOILET TO THE RIGHT OF THE LAB. IS THIS | | | EXTENSION FOR THE STORAGE AREA OUTSIDE OF THE LAB? | | | | | | 3) THE EXISTING HP-2 APPEARS TO HAVE A DAMPER FOR A | | | RETURN IN EXAM 3 BUT THERE IS NO DUCT TIED TO THE | | | RETURN GRILLE. | | | | | | 4) THE EXISTING HP-5 HAS A DAMPER FOR A RETURN AIR DUCT | | | AT THE END OF THE 8 X 12 DUCT BUT IT DOESN?T CONNECT TO | | | A RETURN AIR GRILLE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|