| Plan Review Notes For Permit 21100610 |
| Permit Number |
21100610 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-19 14:43:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE APPEARS TO A 12' WIDTH DIMENSION FOR THE | | | ENTRANCE & EXIT. | | | | | | THE MINIMUM WIDTH FOR A FIRE LANE AND FD ACCESS IS 20'. | | | LESSER DIMEENSION MAY BE APPROVED BY THE AHJ. | | | | | | 12' IS TOO NARROW AND THE RISK OF DAMAGE TO THE | | | STRUCTURES & APPARATUS MAY OCCUR AND NEEDS TO BE | | | INCREASED. | | | | | | PLEASE REIVEW AND PROVIDE GREATER DETAIL OF THE | | | EXISTING ENTRANCE & EXIT AND HOW THE FD CURRENTLY | | | ACCESSES THROUGH. | | | | | | FOR CLARIFICATION, PLEASE PROVIDE HOW THE PROPOSED IS | | | EQUAL OR IMPROVES THE EXISTING SETUP. | | | | | | | | | | | | 1A) IS THIS A 24 HOUR ATTENDED SECURITY FOR 24HR FD | | | ACCESS OR IS A KNOX KEY SWITCH EXISTING AND WILL BE | | | PROVIDE WITH THE PROPOSED? | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|