Plan Review Notes
Plan Review Notes For Permit 21100604
Permit Number 21100604
Review Stop E
Sequence Number 1
Notes
Date Text
2021-11-03 14:17:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FBC R314 SMOKE ALARM IS REQUIRED PER FBC.
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
  
 2) LIGHTING OUTLET IS REQUIRED BY 210.70 OF THE NEC
  
 210.70(A)(1) HABITABLE ROOMS. AT LEAST ONE WALL
 SWITCH?CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE
 ROOM,
 KITCHEN, AND BATHROOM.